Battery replacement
4. Replacement of the batteries should be performed only by people confident with the task who have
read and understood the safety precautions. If you have any doubts about the task, please contact local
technicians.
5. Prior the work, remove watches, rings and other metal objects, and only use insulated tools.
6. Turn off the UPS, disconnect it from the input and output and wait for 10minutes to allow discharging
all internal capacitors.
7. Some models offer easy access to batteries, where all PCBAs are guarded from the user. Otherwise, the
UPS’ enclosure needs to be open. Take additional care not to touch components on PCBA, terminals or
any metal parts.
8. Do not short-circuit the battery terminals.
9. Use batteries with the same specifications as the ones originally installed. Replace all batteries at once
(do not replace only one battery from the set).
10. Do not open batteries. Released electrolyte is toxic to the skin and eyes.
11. Do not dispose of batteries in a fire. The battery may explode.
12. To dispose properly the used battery, please do not dispose the UPS or battery packs into the trash bin.
Please follow your local laws and regulations; you may contact your local recycling waste management
centre for further information.
IX. Troubleshooting
1. If a short on the output or input has caused the circuit breaker to trip, remove the connections on the
input and output, engage the breaker again and turn on the UPS in the DC mode. If no issues were
reported, connect the UPS to input. If no issues were reported, connect your devices on the output
one by one to the UPS.
2. If an overload is detected, an audible alarm will sound. To correct this, turn the UPS off and unplug at
least one piece of equipment from the outlets. Check if the breaker is engaged and turn on the UPS.
3. Check Frequently Asked Questions at http://faq.powerwalker.com
to find additional guidance.
4. In case smoke is found coming out from the device, please cut off the power supply and contact the
service.
5. Please check general troubleshooting instruction at http://troubleshoot.powerwalker.com
and return
with feedback to our service support system at http://support.powerwalker.com. Make sure you have
collected and provided all necessary information.
X.
Storage and transportation
1. Make sure the battery is fully charged before the UPS is stored.
2. Turn off the UPS and disconnect its power cord from the wall outlet. Disconnect all output cables.
3. The UPS should be stored in a cool dry location.
4. For extended storage in moderate climates, the battery should be charged for several hours every three
months by plugging the UPS to the power socket. Repeat it every two months in high-temperature
locations.
5. For extended storage, we recommend covering the UPS to protect it against the dust or preferably to
pack into original foil, cushions and box.

Chat with your PowerWalker VFI 2000 AT FR manual using AI

Get instant AI answers from your PowerWalker VFI 2000 AT FR manual

Ask anything about the PowerWalker VFI 2000 AT FR. Answers come from this manual, with the pages they are based on.

VFI 2000 AT FR Maintenance Schedule

Remind me when maintenance is due
Monthly
Monitor battery condition after two years of use

After two years, strictly monitor battery state monthly. If discharge time is less than 50% of rated value, replace batteries.

Every 2 Months
Recharge battery during high-temp storage

For locations with high temperature, repeat the charging cycle every two months.

Quarterly
Recharge battery during long-term storage

For moderate climates, recharge battery every three months by plugging in for several hours.

As needed / Dusty environments
Clean the USV exterior and vents

Keep area clean. If dusty, vacuum exterior. Unplug before cleaning. Use dry soft cloth for front panel and air intakes.

Free maintenance reminders

Timed to your purchase date. Always free, unsubscribe anytime.

By submitting you agree to the privacy policy. Unsubscribe with one click in any email.
M: qwen/qwen3.8-flash

Ask a Question

0/1000

Do you recommend VFI 2000 AT FR?

Yes No

Frequently Asked Questions

A

The design life is three to five years from the date of production. You should monitor battery condition frequently after two years to ensure reliability.

Is this answer helpful?

A

No, the USB port and RS-232 port cannot work at the same time. You must choose one for communication.

Is this answer helpful?

A

ECO mode bypasses input to output for energy saving when input voltage is within the set range. It offers higher efficiency in line mode.

Is this answer helpful?

A

Unplug the UPS prior to cleaning. Use dry soft clothes for the front panel and plastic parts. Do not use liquid or spray detergent.

Is this answer helpful?

A

Yes, the DC Start Function enables the UPS to be started up when AC utility power is not available and the battery is charged.

Is this answer helpful?

A

Warning occurs at 105-110% overload. Shutdown happens after one minute at 110-130% and after 3 seconds above 130%.

Is this answer helpful?

A

Yes, selected models include RJ11/RJ45 surge protection for connecting modems or phone lines to protect equipment from communication surges.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Dual communication ports allow flexible monitoring via USB or serial connections for system integration.
  • Automatic Voltage Regulation boosts low or bucks high voltage to protect connected devices from fluctuations.
  • Pure sine wave output ensures compatibility with sensitive equipment like servers and medical devices.
  • ECO mode increases efficiency when input voltage is within normal ranges without compromising power stability.
  • Clear LCD display provides immediate insight into input voltage, output frequency, and remaining battery capacity.
VS

Disadvantages

  • USB and serial ports cannot function simultaneously which may limit specific monitoring setups requiring both.
  • Batteries have a design life of three to five years meaning frequent monitoring is needed after two years.
  • Overload protection shuts down units quickly if limits are exceeded which may interrupt critical processes.
  • Some internal settings like battery pack count require manual configuration during initial setup phases.
  • EPO wiring requires building safety integration knowledge and proper termination to function correctly.
M: QW-35-FL

Product Specification

Type

Tower

Classification

VFI (On-Line)

Apparent Power

2000VA

Real Power

1800W

Voltage

208V, 220V, 230V, 240V

Input

C14

Outputs

4x Type E

Interfaces

USB, serial

Charging Time

4h (90%)

Weight

37.70 lbs

Dimensions (WxHxD)

5.94x8.86x15.35in

Features

LCD, HID Support

M: QW-35-FL

Product Description

BlueWalker PowerWalker VFI 2000 AT FR Overview

Keeping your critical equipment safe from sudden power failures is essential for uninterrupted business continuity in modern offices. The BlueWalker PowerWalker VFI 2000 AT FR offers robust protection for sensitive electronics in industrial and commercial settings. This Uninterruptible Power Supply ensures stability during sudden outages or damaging voltage spikes from the grid. It protects servers and networking gear effectively from damage.

Advanced Connectivity Features

Users benefit from flexible communication options including USB and serial ports on the rear panel. These features allow remote monitoring and control via appropriate software or generic system drivers. You can set the operating system to sleep or shut down automatically when battery levels drop low. Real-time data on load percentage, voltage, and frequency is clearly visible on the integrated LCD panel. This visibility helps maintain system health proactively.

Safety and Installation Guidelines

Always install the unit near an easily accessible power outlet for emergency access during incidents. Ensure the ground connection is secure to avoid electrical shock hazards during regular operation. Do not allow liquids or foreign objects near the device enclosure to prevent malfunctions. Follow local electrical regulations strictly during installation processes. The unit generates heat during use so keep cooling vents clear of dust accumulation. Avoid combustible gases or high humidity environments completely.

Operation Tips for Reliability

Leave the unit plugged in continuously to recharge the battery system effectively for future use. Recharging takes at least six hours for first time full capacity under normal conditions. Keep ambient temperature around 25 degrees Celsius for maximum battery longevity over years. Plan your connected load below 80% of rated capacity for safety margins during peaks. Avoid exceeding 30% load for optimal system energy performance and efficiency.

Maintenance Notes

Clean the exterior casing with a dry cloth on a regular basis to remove dust. Replace batteries only by qualified technicians who fully understand safety precautions and requirements. Batteries typically last between three to five years based on original production date. Monitor capacity monthly once the unit passes two years of service in the field. Dispose of used batteries according to strict local recycling laws and environmental guidelines.

Troubleshooting Support

Check LCD displays for error codes if significant issues arise unexpectedly. E11 or E12 often indicate battery connection problems or faults within the pack. E14 suggests load issues such as shorts or excessive current draw from devices. Smoke requires immediate power cut and contacting qualified service personnel promptly. Consult online resources for specific fault codes and resolution steps. Ensure ventilation is never blocked during operation.