Manual.ly Logo

Benning DUTEST pro Manual

5.0 · 5 Ratings

PDF manual · 52 Pages

English

M: OA-GPT-54-NAN
page

/ 52

Loading...
bf65caf986d0e5621c8af42d458646f35adc page 5
05/ 2018
DUTEST
®
pro
D D
2
Funktionen einwandfrei funktionieren!
4. Durchgangs-undDiodenprüfung
- Die Durchgangs- und Diodenprüfung ist an span-
nungsfrei geschalteten Anlagenteilen durchzufüh-
ren, ggf. sind Kondensatoren zu entladen.
- Legen Sie die beiden Prüfspitzen
7
und
8
an die
zu prüfenden Anlageteile.
- Bei Durchgang (Widerstandswert R ≤ 100 Ω -
200Ω)ertönteinSignaltonunddiegelbenLED’s
1
,
2
und
3
leuchten auf.
- Anhand der LED-Stufenanzeige
1
,
2
und
3
kann die Höhe des Widerstandswertes grob ein-
geschätzt werden.
Widerstand (R):
≤100Ω
-
200Ω
≤1kΩ ≤10kΩ
>10kΩ
≤100kΩ
Summer:
1
LED100Ω
● 1.●↓
2
LED1kΩ
● ● 2.●↓
3
LED10kΩ
● ● ● 3.●↓
- Um die Durchlassrichtung einer Diode zu bestim-
men, legen Sie die schwarze - Prüfspitze
8
an
die Kathode und die rote + Prüfspitze
7
an die
Anode der Diode. Die Durchlassrichtung ist
bestimmt, wenn die gelben LED’s
1
,
2
und
3
im
Lauflicht leuchten.
- Sollte an der Prüfstelle eine Spannung anliegen,
warnt das Gerät durch das Aufleuchten der roten
LED’s
4
und/oder
5
vor dem Anliegen einer
Fremdspannung. Die Prüfung ist sofort zu stop-
pen und die Spannungsfreiheit ist herzustellen!
Einstellung der Summerlautstärke
Die Lautstärke des Summers kann in vier Stufen ein-
gestellt werden. Stufe 1 (leise), Stufe 2 (mittel), Stufe
3 (laut) und Stufe 4 (sehr laut). In Stufe 5 ist der Sum-
mer: AUS, die LED-Taschenlampe: AN.
Zur Einstellung der Lautstärke schließen Sie die Prüf-
spitzen
7
und
8
kurz und halten Sie den Taster
gedrückt bis die gewünschte Lautstärke eingestellt
ist. Die eingestellte Summerlautstärke bleibt bis zur
nächsten Änderung gespeichert.
5. Fremdspannungs-undPolaritätsanzeige
- Legen Sie die beiden Prüfspitzen
7
und
8
an die
zu prüfenden Anlageteile.
- Die Fremdspannungsanzeige LED’s
4
und
5
erkennt Gleich- ( ) und Wechselspannungen
() in einem Bereich von 6 V - 400 V.
- Wechselspannungen () werden über das gleich-
zeitige Aufleuchten der + LED
4
und der - LED
5
angezeigt.
- Gleichspannungen ( ) werden durch das Auf-
leuchten der + LED
4
oder der - LED
5
ange-
zeigt. Die + LED
4
leuchtet, wenn der Pluspol
der Spannungsquelle an die rote + Prüfspitze
7
und der Minuspol der Spannungsquelle an die
schwarze - Prüfspitze
8
angelegt wird.
Achtung!
Die Fremdspannungsanzeige ersetzt keinen zwei-
poligen Spannungsprüfer zur Feststellung der Span-
nungsfreiheit.
Zusatzanzeige für Fremdspannungserkennung
(zweipolig)
Ist der Summer bei der Durchgangsprüfung einge-
schaltet, warnt ein pulsierender Signalton vor dem
Anliegen einer Fremdspannung. Ist der Summer bei
der Durchgangsprüfung ausgeschaltet, blinkt die LED-
Taschenlampe beim Anliegen einer Fremdspan-
nung. Die Zusatzanzeige (pulsierender Signalton bzw.
blinkende LED-Taschenlampe ) ist deaktivierbar.
Legen Sie hierzu die beiden Prüfspitzen
7
und
8
an
eine Spannungsquelle (6 V - 400 V) und betätigen Sie
den Taster für ca. 1 s. Zum Aktivieren der Zusatz-
anzeige (pulsierender Signalton bzw. blinkende LED-
Taschenlampe ) wiederholen Sie den Vorgang.
6. EinpoligeAußenleiterprüfung(Phase)
- Legen Sie die schwarze - Prüfspitze
8
oder die
rote + Prüfspitze
7
an das zu prüfende Anlagen-
teil. Achten Sie unbedingt darauf, dass bei der
einpoligen Außenleiterprüfung (Phase) die blanke
Prüfelektrode
6
der anderen Prüfspitze nicht
berührt wird und diese kontaktfrei bleibt.
- Wenn die rote LED
4
blinkt, liegt an diesem
Anlagenteil der Außenleiter (Phase) einer Wech-
selspannung.
ZusatzanzeigefürAußenleiterprüfung
Im Bedarfsfall kann eine Zusatzanzeige (pulsierender
Signalton bzw. blinkende LED-Taschenlampe ) für
die Außenleiterprüfung aktiviert werden. Zum Aktivie-
ren kontaktieren Sie die schwarze - Prüfspitze
8
oder
die rote + Prüfspitze
7
mit dem Außenleiter (Phase)
einer Steckdose und betätigen Sie den Taster für
ca. 1 s. Zum Deaktivieren der Zusatzanzeige betätigen
Sie den Taster erneut. Die Zusatzanzeige (pulsie-
render Signalton bzw. blinkende LED-Taschenlampe
) ist abhängig von der eingestellten Summerlaut-
stärke der Durchgangsprüfung. (siehe Kapitel 4).
Hinweis:
Die einpolige Außenleiterprüfung (Phase) ist im geer-
deten Netz ab 230 V, 50 Hz/ 60 Hz (Phase gegen
Erde) möglich.
7. Kabelbruchdetektor
- Der Kabelbruchdetektor lokalisiert berührungs-
los Kabelbrüche an offenliegenden und unter
Spannung stehenden Leitungen.
- Führen Sie den Detektor über eine spannungs-
führende Leitung (z.B. Kabeltrommel oder Lichter-
kette), von der Einspeisestelle (Phase) Richtung
dem anderen Leitungsende.
- Solange die Leitung nicht unterbrochen ist, blinkt
die rote LED
4
auf.
- Die Kabelbruchstelle ist lokalisiert, sobald die rote
LED
4
erlischt.
ZusatzanzeigefürKabelbruchdetektor
Eine aktivierte Zusatzanzeige (pulsierender Signalton
bzw. blinkende LED-Taschenlampe ) bei der einpo-
ligen Außenleiterprüfung (siehe Kapitel 6) ist ebenfalls
für den Kabelbruchdetektor aktiv.
Hinweis:
Der Kabelbruchdetektor kann im geerdeten Netz ab
230 V, 50 Hz/ 60 Hz (Phase gegen Erde) eingesetzt
werden.
8. LED-Taschenlampe
Achtung!
Möglicherweise gefährliche optische
Strahlung!Nichtdirektoderindirektüber
reflektierendeOberflächenin denStrahl
blicken,Netzhautgefährdung!
- Das Gerät besitzt eine punktgenaue Hochleis-
tungs-LED-Taschenlampe , die durch Betäti-
gung des Tasters ein- oder ausgeschaltet wer-
den kann.
- Die Ausschaltung erfolgt automatisch nach ca. 2
Min.
EinstellungderLeuchtstärke
Die Leuchtstärke der LED-Taschenlampe kann in
vier Stufen eingestellt werden.
Stufe 1 (25 %), Stufe 2 (50 %), Stufe 3 (75 %) und

Chat with your Benning DUTEST pro manual using AI

Get instant AI answers from your Benning DUTEST pro manual

Ask anything about the Benning DUTEST pro. Answers come from this manual, with the pages they are based on.

DUTEST pro Maintenance Schedule

Before and after each use
Check device function

Press the button for approx. 5 seconds to test all LEDs, torch, and buzzer. Short-circuit probes to verify internal circuit and batteries.

When needed
Replace batteries

Replace batteries immediately if the continuity test LEDs flash during the functional check.

As required
Clean exterior housing

Wipe the outside of the device with a clean dry cloth to remove dirt or deposits.

As required
Clean battery area

Clean any contamination or deposits around the battery compartment with a dry cloth.

During long storage
Remove batteries

Take the batteries out of the device if it will not be used for an extended period.

M: QW-35-FL

Ask a Question

0/1000

Do you recommend DUTEST pro?

Yes No
0
User Pic

Destiney Halvorson

10 months ago

Does this tester provide both optical and acoustic continuity signaling, and is it compact enough for regular electrician use?

0
User Pic

Manual.ly

10 months ago

Yes. It is designed for many test applications and performs continuity (through-connection) checks with both visual (optical) and audible (acoustic) feedback. The signal is provided in stages, so you can quickly see and hear the result during line checks. Reviewers also describe it as small and handy for everyday use in the field, which makes it comfortable when working on cables. Note: one user mentioned the housing plastic feels less premium, but overall it is considered to do its job reliably.

M: OA-GPT-54-NAN
M: OA-GPT-54-NAN

Frequently Asked Questions

A

It supports continuity tests, diode tests (including direction indication), external voltage detection for AC/DC with polarity, a single-pole phase check, and non-contact cable-break localization.

Is this answer helpful?

A

The external voltage indication covers 6 V to 400 V for both AC and DC (50/60 Hz). Red LEDs show whether the detected voltage is AC or DC and also provide polarity information.

Is this answer helpful?

A

No. The external-voltage indication warns about present voltage, but it does not replace a two-pole voltage tester to verify the absence of voltage before working.

Is this answer helpful?

A

Continuity uses a buzzer plus three yellow LED steps corresponding to resistance ranges (low ohms to higher ohms). Diode direction is identified by applying probe polarity so the yellow LEDs illuminate in the conducting state.

Is this answer helpful?

A

It locates cable breaks non-contact by scanning along an exposed live line from the feeding end toward the other end. While the line is unbroken, the red indicator flashes; when the break point is reached, the indicator goes out.

Is this answer helpful?

A

Yes. The torch has four brightness levels (25%, 50%, 75%, 100%). The buzzer volume can be set in multiple steps, including a setting that turns the buzzer off while keeping the torch on.

Is this answer helpful?

M: OA-GPT-54-NAN

Advantages and Disadvantages

Advantages

  • Continuity testing with buzzer plus three yellow LED ranges for low-resistance checks
  • Diode testing with conducting-direction indication using probe polarity
  • External voltage detection for AC and DC from 6 V to 400 V with polarity LEDs
  • Single-pole phase test and non-contact cable break detection for practical troubleshooting
  • Built-in high-power LED torch with four brightness levels and adjustable buzzer volume
VS

Disadvantages

  • External-voltage indication does not replace a two-pole voltage tester for proving voltage absence
  • Continuity and diode testing require de-energized parts (and discharge of capacitors if needed)
  • Continuity resistance result is rough (LED steps with tolerance around the max LED step value)
  • Single-pole phase and cable break functions are intended for specific grounded mains conditions
  • IP40 protection is limited; device must be kept dry and protected from condensation
M: OA-GPT-54-NAN

Product Specification

Measurement Range

6-400V

M: GO-GEM-FL-25

Product Description

Benning Dutest Pro Voltage tester - Manual

The Benning Dutest Pro Voltage tester is a rugged, electrician-focused tool designed for fast, visual and acoustic diagnostics during installation and maintenance. Using two insulated test probes, it helps you check continuity, test diodes, identify external voltage, determine polarity, perform a single-pole phase check, and locate cable breaks without direct contact. The Benning Dutest Pro Voltage tester Manual highlights how the device combines multiple functions into one compact tester, so field work moves quickly and confidently.

For continuity checks, the tester uses a three-step yellow LED scale plus a buzzer. Depending on the measured resistance range, different LED levels illuminate, giving a rough estimate of whether the connection is low-ohmic or likely open. It also supports diode testing and can indicate diode direction by switching probe polarity, with the yellow LEDs showing the conducting state.

Safety and awareness are core parts of the design. Red LEDs provide external voltage indication for both AC and DC in the 6 V to 400 V range (50/60 Hz). Polarity is displayed with the corresponding plus and minus LEDs. The device emphasizes that external-voltage indication does not replace a two-pole voltage tester for confirming the absence of voltage.

For phase work, the single-pole external conductor test (phase) indicates whether an AC phase is present, while an integrated cable-break detector can find local breaks along exposed live lines by tracking where the signal disappears. This makes the Benning Dutest Pro Voltage tester especially useful for troubleshooting lighting strings, cable reels, and other in-field circuits.

A built-in high-power LED torch adds convenience when working in dark panels or cramped spaces. You can switch it on and off and set brightness in four levels (25%, 50%, 75%, 100%). The buzzer volume is also adjustable across multiple steps, including a mode that turns the buzzer off while keeping the torch on.

Key results

  • Continuity and diode testing with a buzzer plus a three-step LED scale for quick pass-or-warn decisions.
  • AC/DC external voltage detection from 6 V to 400 V, with polarity indication via dedicated LEDs.
  • Single-pole phase checking and a non-contact cable-break detector for faster troubleshooting.
  • CAT III 300 V safety design plus an IP40 housing for protected everyday use.

Notes

  • Continuity and diode tests must be performed on de-energized system parts; stop immediately if external voltage is detected.
  • IP40 means avoid moisture, wet conditions, and condensation.
  • Replace batteries when the continuity LEDs flash; keep the battery compartment closed during operation.
M: OA-GPT-54-NAN