b4e94240dd440041b31a08a737180fd7e5db page 1
Operating Instructions
Device tester GT-6000 v2
Item No. 2362387 Page 2 - 34

Chat with your Voltcraft GT-6000 V2 manual using AI

Get instant AI answers from your Voltcraft GT-6000 V2 manual

Ask anything about the Voltcraft GT-6000 V2. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend GT-6000 V2?

Yes No
0
User Pic

Lars Wendt

5 months ago

Does this tester measure the actual leakage/protective conductor current while the appliance is operating, rather than only using a substitute leakage test?

0
User Pic

Manual.ly

5 months ago

Yes. It uses a differential current method to measure the actual leakage or protective conductor current under load. This allows the complete connected appliance to be tested, including devices that can only be switched on with mains voltage. Its straightforward operation also avoids complicated menu navigation.

M: gpt-5.6-terra
M: gpt-5.6-terra
0
User Pic

Markus Klein

5 months ago

Does this tester measure actual leakage/protective conductor current under load, and is it easy to operate?

0
User Pic

Manual.ly

5 months ago

Yes. It uses the differential current method to measure the actual leakage or protective conductor current while the appliance is operating, enabling a more complete test. Its operation is intentionally straightforward, without complex menu navigation. This can be especially useful for equipment that must be powered by mains voltage before it can be switched on.

M: gpt-5.6-terra
M: gpt-5.6-terra

Frequently Asked Questions

A

It tests portable appliances in protection classes 1, 2, and 3, plus IEC leads, extension cables, cable reels, multi-plugs, earthed outlets, and 30 mA RCDs. With optional adapters, it can also test three-phase equipment.

Is this answer helpful?

A

The tester measures protective conductor resistance, insulation resistance, substitute leakage current, differential leakage current, contact current, outlet voltage, cable continuity, cable short circuits, and RCD tripping time.

Is this answer helpful?

A

Yes. Insulation resistance testing can be set to 500 V DC or 250 V DC. The 250 V setting is useful where a higher test voltage may be unsuitable for the equipment under test or its built-in protective components.

Is this answer helpful?

A

The internal memory stores up to 999 appliance test records. Saved values can be recalled on the tester or downloaded to a Windows-compatible computer through the USB-C interface and Voltcraft PAT software.

Is this answer helpful?

A

Yes. It tests 30 mA permanently installed and portable RCDs at 30 mA and 150 mA, with both 0 degree and 180 degree initial polarity. Preset limits are 200 ms at 30 mA and 40 ms at 150 mA.

Is this answer helpful?

A

No. Three-phase testing is supported with optional measurement adapters. Passive adapters are used for selected resistance and equivalent leakage checks, while an active 16 A CEE adapter supports operating-condition leakage testing.

Is this answer helpful?

M: gpt-5.6-terra

Advantages and Disadvantages

Advantages

  • Combines appliance, cable, socket outlet, RCD, and optional three-phase testing in one tester.
  • Provides automatic pass/fail assessment using preset limits for common electrical safety tests.
  • Selectable 250 V DC or 500 V DC insulation testing supports a wider range of equipment.
  • Stores up to 999 test records and transfers results to a Windows computer through USB-C.
  • Battery operation supports substitute leakage testing and approximately 2500 tests with fresh batteries.
VS

Disadvantages

  • Three-phase testing requires optional passive or active measurement adapters.
  • The unit is intended for dry indoor use only and has an IP40 protection rating.
  • Stored records can only be erased as a complete memory, not individually.
  • RCD testing is specified for 30 mA RCCBs/RCDs and PRCDs.
  • Safe operation requires electrical knowledge and strict adherence to applicable standards.
M: gpt-5.6-terra

Product Description

Voltcraft GT-6000 V2 Voltage Tester - Read, Download & Print Free

The Voltcraft GT-6000 V2 Voltage Tester is a practical electrical safety tester designed for checking portable appliances, power leads, socket outlets, and residual current devices. Built for professional testing routines, it helps technicians assess equipment against common electrical safety requirements, including DIN VDE 0701-0702, DGUV Regulation 3, OVE/ONORM E 8701, and NEN 3140.

Comprehensive Appliance Safety Tests

This tester supports protection class 1, class 2, and class 3 equipment. It measures protective conductor resistance, insulation resistance, differential leakage current, contact current, and substitute leakage current. Clear pass or fail indications compare results against preset limits, helping users identify whether an appliance needs further inspection.

For insulation checks, the GT-6000 V2 offers selectable 250 V DC and 500 V DC test voltages. The lower setting is useful when testing equipment with sensitive electronics, surge protection, or components that may not be suitable for a 500 V test. Protective conductor resistance testing uses a test current above 200 mA, supporting reliable earth continuity checks.

Cable, Socket, and RCD Testing

Beyond appliance testing, the Voltcraft GT-6000 V2 can inspect IEC power cables, extension leads, cable reels, and multi-plugs. It checks earth continuity, insulation resistance, conductor breaks, and short circuits between line and neutral conductors. A mains outlet test also displays L-N, L-PE, and N-PE voltages to provide a quick initial assessment of an earthed socket.

The integrated RCD function measures tripping times for 30 mA permanently installed RCCBs/RCDs and portable RCCBs/PRCDs. It tests at both rated 30 mA and five-times-rated 150 mA fault currents, using 0 degree and 180 degree initial polarity. This makes the unit useful for routine verification of protective switching devices.

Data Storage and Transfer

Up to 999 test records can be stored in internal memory. Results can be recalled on the display or transferred to a Windows-compatible computer through USB-C using Voltcraft PAT software. Export support for spreadsheet-compatible XLS files can simplify record keeping and reporting. An integrated real-time clock helps associate stored results with the correct date and time.

Practical Design for Field Work

The tester has a large LCD, backlight, color-based PASS and FAIL illumination, supplied alligator test lead, IEC cables, carrying pouch, and battery operation for mobile use. Optional adapters extend its capability to passive and active three-phase device testing. Always follow applicable safety procedures and ensure tests near energized systems are carried out by qualified personnel.

Notes

  • Use only in dry indoor environments within the specified measurement category.
  • Annual calibration is recommended to maintain stated measurement accuracy.
  • Remove batteries before long-term storage to reduce the risk of leakage damage.
M: gpt-5.6-terra