M: QW-35-FL
page

/ 2

Loading...
5e06613fb23c6e5ec3d0c8257912964b176e page 1
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: + 49 - 2263 - 880
•
Fax: + 49 - 2263 - 4588
•
•
www.mdt.de
Stand: 1120
Technische Änderungen und Irrtümer vorbehalten,
Abbildungen können abweichen.
Allgemeine Sicherheitshinweise - Important safety notes Lebensgefahr durch elektrischen Strom - Danger High Voltage
• Das Gerät darf nur von Elektrofachkräften montiert und angeschlossen werden. Beachten sie die länderspezischen
Vorschriften sowie die gültigen KNX-Richtlinien. Die Geräte sind für den Betrieb in der EU zugelassen und tragen das CE
Zeichen. Die Verwendung in den USA und Kanada ist nicht gestattet. Installation and commissioning of the device
only be carried out by authorised electricans. The relevant standards, directives, regulations and instructions must be
observed. The devices are approved for use in the EU and have the CE mark. Use in USA and Canada is prohibited.
• Nach dem Einbau des Gerätes und Zuschalten der Netzspannung kann an den Ausgängen Spannung anliegen.
Über eingebauten Kanaltaster lassen sich die Ausgänge ausschalten. After Installation and connecting mains power
supply the outputs can be alive. The outputs can be switched OFF using the push buttons on top of the device.
• In eingebauten Zustand kann ein KNX-Bustelegramm die Ausgänge jederzeit spannungsführend schalten.
After installation a KNX bus telegram can switch the outputs alive.
• Vor Arbeitsbeginn am Gerät immer über die vorgeschalteten Sicherungen spannungsfrei schalten.
Disconnect the mains power supply prior to installation or disassembly.
• Alle spannungsführenden Klemmen und Anschlüsse müssen nach der Installation vollständig durch die Schalttafel-
abdeckung berührungssicher verschlossen werden. Die Schalttafelabdeckung darf nicht ohne Werkzeug zu öffnen sein.
All screw terminals and connections under current must be covered completely against touching by the switch panel.
It should not be possible to open the switch panel cover without using tools.
Anschlussklemmen, Bedien- und Anzeigeelemente Schaltakor AKK
Terminals, Operating and Display Switch Actuator AKK
Technische Daten
Technical Data
AKK-0216.03
AKK-0416.03
AKK-0816.03
AKK-1616.03
AKK-2416.03
Anzahl Ausgänge
Number of outputs
2/4 8/16/24
Maximale Schaltleistung
Output switching ratings
Ohmsche Last
Ohmic load
16A 16A
Kapazitive Last
Capacitive load
70µF 70µF
Spannung
Voltage
230VAC 230VAC
Maximaler Einschaltstrom
Maximum inrush current
300A/150µs
150A/600µs
300A/150µs
150A/600µs
Maximale Last
Maximum lamp loads
Glühlampen
Incandescent lamps
2000W 2000W
HV- Halogenlampen
Halogen lamp 230V
2000W 2000W
NV- Halogenlampen
Halogen lamp, electronic transformer
1200W 1200W
Leuchtstofampen unkompensiert
Fluorescent lamp not compensated
1800W 1800W
Leuchtstofampen parallelkompensiert
Fluorescent lamp parallel compensated
800W 800W
max. Anzahl EVG
max. number of electronic transformers
10 10
mech. Schalthäugkeit
Output life expectancy (mech.)
1.000.000 1.000.000
Summenstrombelastbarkeit des Aktors
max. total current of the actuator
16A/16A 50A/100A/125A
Spezikation KNX Schnittstelle
Specication KNX interface
TP-256 mit Long Frame Unterstützung für
ETS5
TP-256 mit Long Frame
Unterstützung für ETS5
Verfügbare KNX Datenbanken
Available application software
ETS 4/5 ETS 4/5
Max. Kabelquerschnitt
Permitted wire gauge
Schraubklemmen (max. 0,5Nm Anzugsmoment)
Screw terminal (max. 0,5Nm tightening torque)
0,5 - 2,5mm²
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
KNX Busklemme
KNX busconnection terminal
0,8mm Ø, solid core 0,8mm Ø, solid core
Anzugsmoment Schraubklemme
Torque screw terminal
0,5Nm 0,5Nm
Versorgungsspannung
Power supply
KNX Bus KNX Bus
Leistungsaufnahme KNX Bus typ.
Power consumption KNX bus
<0,3W <0,3W
Umgebungstemperatur
Operation temperature range
0 bis + 45°C 0 bis + 45°C
Schutzart
Enclosure
IP 20 IP 20
Abmessungen REG
Dimensions REG
2/2TE 4/8/12TE
Technische Daten Schaltaktor AKK - Technical Data Switch Actuator AKK
5 6
AKK-0216.03
Betriebsanleitung Schaltaktor AKK - nur für autorisiertes Elektrofachpersonal
Operating Instructions Switch Actuator AKK - for authorised electricans
1 - Busanschlussklemme
- KNX busconnection terminal
2 - Programmiertaster
- Programming key
3 - Rote Programmier LED
- Red programming LED
4 - Anschlussklemmen
- Output power terminal
5 - Grüne Kanalanzeige LED
- Green ON/OFF Led
6 - Taster Handbetätigung
- Buttons for manual actuation
1
2
3
4
AKK-0416.03 AKK-0816.03
1 1
2
3
2
3
4
4
5
5
6
6
®

Chat with your MDT Compact 16A manual using AI

Get instant AI answers from your MDT Compact 16A manual

Ask anything about the MDT Compact 16A. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend Compact 16A?

Yes No

Frequently Asked Questions

A

The device supports up to 24 independent outputs depending on the specific model variant selected.

Is this answer helpful?

A

Yes, each channel has a dedicated push button for manual actuation regardless of bus status.

Is this answer helpful?

A

No, the device is only approved for the EU market and its use in the USA and Canada is prohibited.

Is this answer helpful?

A

Relays maintain their current position during a bus failure, and settings restore based on configuration upon power return.

Is this answer helpful?

A

You need ETS 4 or ETS 5 application software to configure parameters and upload data to the device.

Is this answer helpful?

A

Each channel can switch up to 16 Amperes of resistive load at 230V AC.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Supports up to 24 independent channels with bistable relays for energy efficiency
  • Compatible with ETS 4/5 software for extensive customization of logic and timing
  • Manual push-button operation allows local control independent of the bus
  • High current capacity handles 16A per channel and manages significant lamp loads
  • Retains switching state during power interruptions for reliable operation
VS

Disadvantages

  • Installation is restricted strictly to authorized electricians due to high voltage risks
  • Not certified for use in North America, limiting global deployment options
  • Requires a protective switch panel cover that cannot be opened without tools
  • Limited to dry indoor environments and standard DIN rail mounting
  • Complex programming may require professional assistance for advanced features
M: QW-35-FL

Product Specification

Type

Actuator

Standard

KNX

Function

Switch actuator (on/off), On/off delay

Topology

Bus

Features

IP20

M: QW-35-FL

Product Description

MDT Switch Actuator Compact 16A: The Core of Intelligent Lighting Control

The MDT Switch Actuator Compact 16A represents a pinnacle in home and building automation technology. Designed for seamless integration into KNX systems, this device serves as the central nervous system for managing electrical loads with precision and reliability. Whether you are controlling lighting in a residential home or managing complex scenes in a commercial office, this actuator delivers consistent performance.

At the heart of the MDT Switch Actuator lies its robust bistable relay technology. This ensures that each of the up to 24 independent channels can be switched reliably without continuous power consumption to maintain the state. The compact design allows it to fit easily onto standard DIN rails within distribution boards, making installation straightforward for electricians. The unit supports various load types, including incandescent, halogen, and fluorescent lamps, handling capacitive loads up to 70 microfarads with ease.

Flexibility is a key feature of this product. Through the ETS software, users can program logical operations, time delays, staircase lighting functions, and scene settings. Each channel can be individually configured to meet specific needs. Additionally, manual control is available via push buttons on the front panel, allowing for direct operation even if the bus communication is temporarily interrupted. Safety is paramount, with strict guidelines requiring installation by authorized personnel only, ensuring compliance with EU regulations and CE marking standards.

Key Highlights

This actuator stands out due to its ability to handle high inrush currents and its memory function during power failures. It retains the last switching position when mains power returns, ensuring your lights behave exactly as expected after an outage. The device operates efficiently on the KNX bus, consuming less than 0.3 watts of power while providing robust connectivity.

Important Notes

  • Installation must be performed by qualified electricians only.
  • The device is approved for use in the EU but prohibited in the USA and Canada.
  • All terminals must be covered by a switch panel that requires tools to open.
  • Outputs can remain live after installation until manually switched off or disconnected.