MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: + 49 - 2263 - 880
•
Fax: + 49 - 2263 - 4588
•
•
www.mdt.de
Stand: 0217
Technische Änderungen und Irrtümer vorbehalten,
Abbildungen können abweichen.
Allgemeine Sicherheitshinweise - Important safety notes Lebensgefahr durch elektrischen Strom - Danger High Voltage
• Das Gerät darf nur von Elektrofachkräften montiert und angeschlossen werden. Beachten sie die länderspezischen
Vorschriften sowie die gültigen KNX-Richtlinien. Die Geräte sind für den Betrieb in der EU zugelassen und tragen das CE
Zeichen. Die Verwendung in den USA und Kanada ist nicht gestattet. Installation and commissioning of the device
only be carried out by authorised electricans. The relevant standards, directives, regulations and instructions must be
observed. The devices are approved for use in the EU and have the CE mark. Use in USA and Canada is prohibited.
• Nach dem Einbau des Gerätes und Zuschalten der Netzspannung kann an den Ausgängen Spannung anliegen.
Über eingebauten Kanaltaster lassen sich die Ausgänge ausschalten. After Installation and connecting mains power
supply the outputs can be alive. The outputs can be switched OFF using the push buttons on top of the device.
• In eingebauten Zustand kann ein KNX-Bustelegramm die Ausgänge jederzeit spannungsführend schalten.
After installation a KNX bus telegram can switch the outputs alive.
• Vor Arbeitsbeginn am Gerät immer über die vorgeschalteten Sicherungen spannungsfrei schalten.
Disconnect the mains power supply prior to installation or disassembly.
• Alle spannungsführenden Klemmen und Anschlüsse müssen nach der Installation vollständig durch die Schalttafel-
abdeckung berührungssicher verschlossen werden. Die Schalttafelabdeckung darf nicht ohne Werkzeug zu öffnen sein.
All screw terminals and connections under current must be covered completely against touching by the switch panel.
It should not be possible to open the switch panel cover without using tools.
Anschlussklemmen, Bedien- und Anzeigeelemente Schaltakor AZI
Terminals, Operating and Display Switch Actuator AZI
Technische Daten
Technical Data
AZI-0316.01 AZI-0616.01
Anzahl Ausgänge
Number of outputs
3 6
Strommeßbereich
Current measurement range
10mA - 20A 10mA - 20A
Messungenauigkeit
Measuring inaccuracy
2% 2%
Abtastrate
Sampling rate
2000 Messungen/500ms
2000 samples/500ms
2000 Messungen/500ms
2000 samples/500ms
Maximale Schaltleistung
Output switching ratings
Ohmsche Last
Ohmic loads
16/20A* 16/20A*
Kapazitive Last
Capacitive loads
200uF bei 16A 200uF bei 16A
Spannung
Voltage
230VAC 230VAC
Maximaler Einschaltstrom
Maximum inrush current
600A/150µs
300A/600µs
600A/150µs
300A/600µs
Maximale Last
Maximum lamp loads
Glühlampen
Incandescent lamps
3680W 3680W
HV- Halogenlampen
Halogen lamp 230V
3680W 3680W
NV- Halogenlampen, elektr. Tranformator**
Halogen lamp, electronic transformer**
2000W 2000W
Leuchtstofampen unkompensiert
Fluorescent lamp not compensated
3680W 3680W
Leuchtstofampen parallelkompensiert
Fluorescent lamp parallel compensated
2500W 2500W
max. Anzahl EVG (elektronischer Trafo)
max. number of electronic transformers
28 28
Mech. Schalthäugkeit
Output life expectancy (mechanical.)
1.000.000
1.000.000
Spezikation KNX Schnittstelle
Specication KNX interface
TP-256
TP-256
Verfügbare KNX Datenbanken
Available application software
ETS 4/5
ETS 4/5
Max. Kabelquerschnitt
Permitted wire gauge
Schraubklemmen
Screw terminal
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
KNX Busklemme
KNX busconnection terminal
0,8mm Ø, solid core 0,8mm Ø, solid core
Anzugsmoment Schraubklemme
Torque screw terminal
0,5Nm 0,5Nm
Versorgungsspannung
Power Supply
KNX bus KNX bus
Leistungsaufnahme KNX Bus typ.
Power consumption knx bus typ.
< 0,4W < 0,4W
Umgebungstemperatur
Operation temperature range
0 bis + 45°C 0 bis + 45°C
Schutzart
Enclosure
IP 20 IP 20
Abmessungen REG (Teilungseinheiten)
Dimensions MDRC (Space Units)
4TE 8TE
1
2
3
4
5
6
AZI-0316.01 AZI-0616.01
1
2
3
4 4
5
6
Betriebsanleitung Schaltaktor AZI - nur für autorisiertes Elektrofachpersonal
Operating Instructions Switch Actuator AZI- for authorised electricans
1 - Busanschlussklemme
- KNX busconnection terminal
2 - Programmiertaster
- Programming key
3 - Rote Programmier LED
- Red programming LED
4 - Anschlussklemmen
- Output power terminal
5 - Grüne Kanalanzeige LED
- Green ON/OFF Led
6 - Taster Handbetätigung
- Buttons for manual actuation
* Summenstrombelastbarkeit benachbarter Ausgänge max. 32A * total current carrying capacity neighbouring outputs max. 32A
** gilt für NV- Halogenlampen mit elektronischem Transformator ** low voltage halogen lamps with electronic transformer
®

Chat with your MDT AZI manual using AI

Get instant AI answers from your MDT AZI manual

Ask anything about the MDT AZI. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend AZI?

Yes No

Frequently Asked Questions

A

The MDT Switch Actuator AZI can independently control up to six different electrical loads depending on the specific model variant installed.

Is this answer helpful?

A

Yes, the AZI features an integrated active power meter that measures consumption in watt-hours and can transmit data in mA, A, or kW formats.

Is this answer helpful?

A

No, installation must only be performed by authorized electricians due to high voltage risks and specific safety regulations regarding KNX systems.

Is this answer helpful?

A

All relays hold their current switching position during a mains voltage failure. Settings upon recovery can be programmed individually per channel.

Is this answer helpful?

A

Yes, each channel has a dedicated push button for manual actuation, with a green LED indicating the current ON/OFF status.

Is this answer helpful?

A

Application software and databases are available for download from the official MDT technologies website under the downloads section.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Supports up to 6 independent outputs with individual programming
  • Integrated current and power measurement for energy monitoring
  • Bistable relays retain state during power outages
  • Manual operation available via front panel push buttons
  • Compatible with ETS 4/5 for easy configuration
VS

Disadvantages

  • Prohibited for use in USA and Canada markets
  • Installation restricted to authorized electricians only
  • Limited to indoor installation in dry rooms
  • Enclosure rating is IP20, not suitable for wet areas
  • Neighboring outputs have a combined current limit of 32A
M: QW-35-FL

Product Specification

Type

Actor

Standard

KNX

Function

Switch actuator (on/off), On/Off delay, Current measurement function

Topology

Bus

Features

IP20

M: QW-35-FL

Product Description

MDT Switch Actuator AZI: Intelligent KNX Control

The MDT Switch Actuator AZI represents a pinnacle of modern building automation, designed to seamlessly integrate with the KNX/EIB standard. This versatile device serves as the backbone for controlling up to six independent electrical loads within a single unit. Whether managing lighting circuits in a residential home or complex industrial setups, the AZI ensures reliable and efficient operation through its robust bistable relay technology.

One of the standout features of the AZI is its comprehensive measurement capabilities. It allows for precise current monitoring on a per-channel basis as well as total current summation. These measurements can be transmitted over the KNX bus in various formats, including milliamps, amps, or kilowatts, providing users with detailed energy data. The integrated active power meter further enables accurate tracking of energy consumption in watt-hours or kilowatt-hours, supporting smart energy management strategies.

Flexibility is at the core of the AZI design. Each output can be individually programmed using ETS software, offering a wide array of functions such as logical operations, status feedback, blocking mechanisms, and central switching commands. Time-based functions like delay switches and staircase lighting timers are also supported, alongside advanced scene control. In the event of a power failure, the relays maintain their last position, ensuring continuity. Upon restoration of power, the system defaults can be configured to suit specific operational needs.

Installation is straightforward for authorized electricians. The unit mounts securely on a standard DIN 35mm rail, making it compatible with most distribution boards. Manual actuation is possible via push buttons located on the front panel, with green LEDs clearly indicating the status of each channel. Safety is paramount, with strict guidelines requiring that all live terminals be covered by a switch panel that cannot be opened without tools.

Key Considerations

When integrating the MDT Switch Actuator AZI into your project, consider the following points regarding performance and installation requirements.

Important Notes

  • Always disconnect mains power before working on the device.
  • Ensure the installation environment is dry and indoors.