MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: + 49 - 2263 - 880
•
Fax: + 49 - 2263 - 4588
•
•
www.mdt.de
Stand: 0321
Technische Änderungen und Irrtümer vorbehalten,
Abbildungen können abweichen.
Technische Daten
Technical Data
AKU-0416.03
AKU-0616.03
AKU-0816.03
AKU-1616.03
AKU-2416.03
Max. Anzahl Schaltausgänge
Number of Switching outputs
4/6/8/16/24
Max. Anzahl Jalousieausgänge
Number of Shutter outputs
2/4/4/8/16
Maximale Schaltleistung
Output switching current
Ohmsche Last
Ohmic load
16A
Kapazitive Last
Capacitive load
100µF
Spannung
Voltage
230VAC
Maximaler Einschaltstrom
Maximum inrush current
400A/150µs
200A/600µs
Maximale Last
Maximum load
Rolladenmotoren*
Shutter motor*
600W
Glühlampen
Incandescent lamps
2300W
HV- Halogenlampen
Halogen lamps 230V
2300W
NV- Halogenlampen**
Halogen lamps, electronic transformer**
1300W
Leuchtstofampen unkompensiert
Fluorescent lamps, not compensated
2000W
Leuchtstofampen parallelkompensiert
Fluorescent lamps, parallel compensated
1200W
Max. Anzahl EVG
Max. number of electronic transformers
15
Mech. Schalthäugkeit
Output life expectancy
1.000.000
Summenstrombelastbarkeit des Aktors
Max. total current of the actuator
64A
Spezikation KNX Schnittstelle
Specication KNX interface
TP-256 mit Long Frame Unterstützung für
ETS5
Verfügbare KNX Datenbanken
Available application software
ETS 5
Max. Kabelquerschnitt
Permitted wire gauge
Schraubklemmen
Screw terminal
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
KNX Busklemme
KNX busconnection terminal
0,8mm Ø, solid core
Anzugsmoment Schraubklemme
Torque screw terminal
0,5Nm
Leistungsaufnahme KNX Bus typ.
Power Consumption KNX bus typ.
< 0,15W
Umgebungstemperatur
Operation temperature range
0 bis + 45°C
Schutzart
Enclosure
IP 20
Technische Daten Universalaktor AKU - Technical Data Universal Actuator AKU
* keine Drehstrommotoren * no three-phase asynchronous motor
1 1
2
2
3
3
4
4 4
5
6
AKU-0816.03 AKU-1616.03
®
Allgemeine Sicherheitshinweise - Important safety notes Lebensgefahr durch elektrischen Strom - Danger High Voltage
• Das Gerät darf nur von Elektrofachkräften montiert und angeschlossen werden. Beachten sie die länderspezischen
Vorschriften sowie die gültigen KNX-Richtlinien. Die Geräte sind für den Betrieb in der EU zugelassen und tragen das CE
Zeichen. Die Verwendung in den USA und Kanada ist nicht gestattet. Installation and commissioning of the device
only be carried out by authorised electricans. The relevant standards, directives, regulations and instructions must be
observed. The devices are approved for use in the EU and have the CE mark. Use in USA and Canada is prohibited.
• Nach dem Einbau des Gerätes und Zuschalten der Netzspannung kann an den Ausgängen Spannung anliegen.
Über die eingebauten Kanaltaster lassen sich die Ausgänge ausschalten. After Installation and connecting mains power
supply the outputs can be alive. The outputs can be switched OFF using the push buttons on top of the device.
• In eingebauten Zustand kann ein KNX-Bustelegramm die Ausgänge jederzeit spannungsführend schalten.
After installation a KNX bus telegram can switch the outputs alive.
• Vor Arbeitsbeginn am Gerät immer über die vorgeschalteten Sicherungen spannungsfrei schalten.
Disconnect the mains power supply prior to installation or disassembly.
• Alle spannungsführenden Klemmen und Anschlüsse müssen nach der Installation vollständig durch die Schalttafel-
abdeckung berührungssicher verschlossen werden. Die Schalttafelabdeckung darf nicht ohne Werkzeug zu öffnen sein.
All screw terminals and connections under current must be covered completely against touching by the switch panel.
It should not be possible to open the switch panel cover without using tools.
Anschlußklemmen, Bedien- und Anzeigeelemente Universalaktor AKU
Terminals, Operating and Display Universal Actuator AKU
Betriebsanleitung Universalaktor AKU - nur für autorisiertes Elektrofachpersonal
Operating Instructions Universal Actuator AKU - for authorised electricans
1 - Busanschlußklemme
- KNX busconnection terminal
2 - Programmiertaster
- Programming key
3 - Rote Programmier LED
- Red programming LED
4 - Anschlußklemmen
- Output power terminal
5 - Grüne Kanalanzeige LED
- Green ON/OFF Led
6 - Taster Handbetätigung
- Buttons for manual actuation
5
6
44

Chat with your MDT AKU-0816.03 manual using AI

Get instant AI answers from your MDT AKU-0816.03 manual

Ask anything about the MDT AKU-0816.03. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend AKU-0816.03?

Yes No

Frequently Asked Questions

A

The AKU family is offered in multiple configurations: 4, 6, 8, 16, and 24 switching outputs to match varying installation sizes.

Is this answer helpful?

A

Yes. Each channel can be configured individually via ETS as a switch or shutter actuator, and mixed configurations are supported to combine lighting and shading control on the same device.

Is this answer helpful?

A

Each channel supports up to 16 A ohmic load; the device handles high inrush currents for lamps and motors, specific wattage limits for incandescent, halogen, fluorescent and electronic transformer loads are documented and total actuator current limits (e.g., up to 64 A) must be observed.

Is this answer helpful?

A

The AKU mounts on a 35mm DIN rail in dry indoor distribution boards. Wiring must be fused externally, connect the KNX bus, assign a physical address and load the ETS application. Press the programming button when prompted; the red LED indicates programming status.

Is this answer helpful?

A

Installation and commissioning must be by authorized electricians. Disconnect mains before service, ensure live terminals are covered, follow national regulations and KNX guidelines. The device is CE-marked for EU use and not permitted for USA/Canada.

Is this answer helpful?

A

Yes. Relay startup positions after bus or mains voltage loss/recovery are parameterizable per channel to define behavior on power events.

Is this answer helpful?

A

MDT provides the necessary application software and KNX database for ETS5 via their download portal; users should download the latest files from the MDT website before commissioning.

Is this answer helpful?

M: OA-GPT-5-NAN

Advantages and Disadvantages

Advantages

  • Modular family with 4–24 outputs to fit small to large installations.
  • Supports mixed switch and shutter configurations per channel.
  • Comprehensive ETS5 parameterization: scenes, delays, logic, PWM heating.
  • High per-channel switching capacity (16A) and strong inrush handling.
  • Manual push-buttons and per-channel status LEDs for local control and diagnostics.
VS

Disadvantages

  • Not approved for use in USA or Canada; CE-marked for EU only.
  • Requires authorized electrician for installation and ETS commissioning.
  • Fixed DIN-rail installation—unsuitable for non-distribution mounting.
  • Outputs can be live after mains apply; careful wiring and enclosure required.
  • No integrated three-phase motor support; limited to single-phase loads.
M: OA-GPT-5-NAN

Product Specification

Type

Actuator

Standard

KNX

Function

Switching actuator (on/off), Blind control

Topology

Bus

Special features

IP20

M: OA-GPT-54-NAN

Product Description

MDT Universal Actor AKU — Powerful, Flexible KNX Actuator

The MDT Universal Actor AKU is a versatile KNX actuator designed for professional building automation. Available in multiple channel configurations (4, 6, 8, 16, 24 outputs), it handles both switching and shutter (blind) tasks and supports mixed configurations so you can combine lighting and shading control in one compact device. Each channel is driven by a bistable relay, provides manual push-button control with green channel status LEDs, and integrates smoothly into KNX systems via TP-256 with Long Frame support for ETS5.

Robust electrical specifications make the AKU suitable for diverse loads: up to 16 A ohmic switching per channel, high inrush current capability for lamps and motors, and clear ratings for incandescent, halogen (electronic and mains), fluorescent, and electronic transformer loads. The unit supports up to 64 A total actuator current (depending on model) and permits many electronic transformers per channel. Wire terminations accept standard solid conductors and the KNX bus terminal is compatible with solid core wiring.

Configurable in ETS, the AKU offers extensive features when used as a switch actuator: logical linking, status feedback, lock functions, central switching, delays, staircase-light timing, scenes, and PWM heating control. When used as a shutter actuator it provides calibration and positioning, ventilation/window tilt handling, scene management (up to 8 scenes per channel), and central functions. Relays’ startup states after bus or mains voltage events are fully parameterizable per channel to meet safety and convenience needs.

Installation is DIN-rail oriented for indoor distribution boards; commissioning demands authorized electricians and ETS programming. The actuator includes a programming button and red LED for programming feedback. Safety notes emphasize disconnecting mains before work, covering live terminals, and compliance with local regulations. The device is CE-marked for EU use (not for USA/Canada).

In short, the MDT Universal Actor AKU is a professional-grade, configurable KNX actuator family that consolidates switching and shutter control, offers broad load compatibility and rich ETS-based functions, and is built for safe installation in electrical distribution systems.

Notes

  • Compatible with ETS5 and available application software via MDT downloads.
  • Intended for fixed installation in dry indoor environments on DIN 35mm rails.
  • Installation and commissioning must be performed by authorized electricians.