dde2b0d413778ab21fe7c597a488e3c502ee page 1
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: + 49 - 2263 - 880
•
Fax: + 49 - 2263 - 4588
•
•
www.mdt.de
Stand: 0421
Technische Änderungen und Irrtümer vorbehalten,
Abbildungen können abweichen.
Allgemeine Sicherheitshinweise - Important safety notes Lebensgefahr durch elektrischen Strom - Danger High Voltage
• Das Gerät darf nur von Elektrofachkräften montiert und angeschlossen werden. Beachten sie die länderspezischen
Vorschriften sowie die gültigen KNX-Richtlinien. Die Geräte sind für den Betrieb in der EU zugelassen und tragen das CE
Zeichen. Die Verwendung in den USA und Kanada ist nicht gestattet. Installation and commissioning of the device
only be carried out by authorised electricans. The relevant standards, directives, regulations and instructions must be
observed. The devices are approved for use in the EU and have the CE mark. Use in USA and Canada is prohibited.
• Nach dem Einbau des Gerätes und Zuschalten der Netzspannung kann an den Ausgängen Spannung anliegen.
Über die eingebauten Kanaltaster lassen sich die Ausgänge ausschalten. After Installation and connecting mains power
supply the outputs can be alive. The outputs can be switched OFF using the push buttons on top of the device.
• In eingebauten Zustand kann ein KNX-Bustelegramm die Ausgänge jederzeit spannungsführend schalten.
After installation a KNX bus telegram can switch the outputs alive.
• Vor Arbeitsbeginn am Gerät immer über die vorgeschalteten Sicherungen spannungsfrei schalten.
Disconnect the mains power supply prior to installation or disassembly.
• Alle spannungsführenden Klemmen und Anschlüsse müssen nach der Installation vollständig durch die Schalttafel-
abdeckung berührungssicher verschlossen werden. Die Schalttafelabdeckung darf nicht ohne Werkzeug zu öffnen sein.
All screw terminals and connections under current must be covered completely against touching by the switch panel.
It should not be possible to open the switch panel cover without using tools.
Anschlussklemmen, Bedien- und Anzeigeelemente Schaltakor AKS 10A
Terminals, Operating and Display Switch Actuator AKS 10A
Technische Daten
Technical Data
AKS-0210.03 AKS-0410.03 AKS-0810.03 AKS-1210.03
Anzahl Ausgänge
Number of Outputs
2 4 8 12
Maximale Schaltleistung je Kanal
Output switching ratings
Ohmsche Last
Ohmic loads
10A
Kapazitive Last
Capacitive loads
140uF
Spannung
Voltage
230VAC
Maximaler Einschaltstrom
Maximum inrush current
600A/150µs
250A/600µs
Maximale Last
Maximum lamp loads
Glühlampen
Incandescent lamps
2200W
HV- Halogenlampen
Halogen lamp 230V
2200W
NV- Halogenlampen*
Halogen lamp, electronic transformer
1400W
Leuchtstofampen unkompensiert
Fluorescent lamp not compensated
2000W
Leuchtstofampen parallelkompensiert
Fluorescent lamp parallel compensated
1400W
max. Anzahl EVG (elektronischer Trafo)
max. number of electronic transformers
20
mech. Schalthäugkeit
Output life expectancy (mech.)
1.000.000
Summenstrombelastbarkeit des Aktors
Max. total current of the actuator
20A 40A 80A 120A
Spezikation KNX Schnittstelle
Specication KNX interface
TP-256 mit Long Frame Unterstützung für ETS5
TP-256 with long frame support for ETS5
Verfügbare KNX Datenbanken
Available application software
ETS 4/5
Max. Kabelquerschnitt
Permitted wire gauge
Schraubklemmen
Screw terminal
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
KNX Busklemme
KNX busconnection terminal
0,8mm Ø, solid core
Anzugsmoment Schraubklemme
Torque screw terminal
0,5Nm
Versorgungsspannung
Power Supply
via KNX bus
Leistungsaufnahme KNX Bus typ.
Power Consumption KNX bus typ.
<0,25W <0,25W <0,25W <0,3W
Umgebungstemperatur
Operation temperature range
0 bis + 45°C
Schutzart
Enclosure
IP 20
Abmessungen (Teilungseiheiten)
Design MDRC (Space Units)
2TE 4TE 6TE 8TE
Technische Daten Schaltaktor AKS 10A - Technical Data Switch Actuator AKS 10A
* gilt für NV- Halogenlampen mit elektronischem Transformator
* low voltage halogen lamps with electronic transformator
1
2
3
4
5
6
AKS-0410.03 AKS-1210.03
1
2
3
4
5
6
Betriebsanleitung Schaltaktor AKS 10A- nur für autorisiertes Elektrofachpersonal
Operating Instructions Switch Actuator AKS 10A - for authorised electricans
1 - Busanschlussklemme
- KNX busconnection terminal
2 - Programmiertaster
- Programming key
3 - Rote Programmier LED
- Red programming LED
4 - Anschlussklemmen
- Output power terminal
5 - Grüne Kanalanzeige LED
- Green ON/OFF Led
6 - Taster Handbetätigung
- Buttons for manual actuation
1
2
3
4
5
6
AKS-0810.03
®

Chat with your MDT AKS 10A manual using AI

Get instant AI answers from your MDT AKS 10A manual

Ask anything about the MDT AKS 10A. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend AKS 10A?

Yes No

Frequently Asked Questions

A

The AKS 10A series includes AKS-0210.03 (2 outputs), AKS-0410.03 (4 outputs), AKS-0810.03 (8 outputs) and AKS-1210.03 (12 outputs), each channel rated for 10 A switching at 230 VAC.

Is this answer helpful?

A

Connect the unit to the KNX TP bus, assign a physical address and load the ETS application. The actuator supports TP-256 with long frame and ETS4/5 application software. Use the programming button and observe the red LED to confirm successful programming.

Is this answer helpful?

A

Install on a 35 mm DIN rail in dry indoor environments. Upstream circuit breakers must protect switching contacts. All live terminals must be covered; the device should be installed and serviced only by qualified electricians following local regulations and KNX guidelines.

Is this answer helpful?

A

Each channel handles 10 A at 230 VAC. Specific limits include incandescent and halogen up to ~2200 W, fluorescent loads up to ~2000 W (uncompensated), and up to ~20 electronic transformers for low-voltage halogen with electronic transformers. Observe total actuator current limits per model (20 A–120 A).

Is this answer helpful?

A

The bistable relays hold their last switching state during bus power loss. After bus recovery, each channel’s relay behavior can be individually configured in ETS to either restore, retain, or set a defined state.

Is this answer helpful?

A

Yes. Each channel has a manual push button for local switching and a green LED indicating the channel’s ON/OFF status. A programming key and red LED are provided for commissioning.

Is this answer helpful?

A

Download the MDT application software and available product database from MDT’s website (www.mdt.de/Downloads.html) to configure the device with ETS before commissioning.

Is this answer helpful?

M: OA-GPT-5-NAN

Advantages and Disadvantages

Advantages

  • High channel density: up to 12 independently switchable outputs in a compact DIN-rail module.
  • Bistable relays: maintain output state during KNX bus power loss for reliable behavior.
  • Per-channel ETS parameterization: supports logic, timers, scenes, feedback and central functions.
  • Wide load compatibility: supports incandescent, halogen, fluorescent and electronic transformers with defined limits.
  • Low KNX bus consumption and simple installation reduce distribution footprint and costs.
VS

Disadvantages

  • EU-only approval: not permitted for use in the USA and Canada.
  • Requires qualified electrician for installation and adherence to local KNX regulations.
  • Outputs can be live after mains or KNX telegrams — upstream isolation mandatory for maintenance.
  • Capacity and lamp limits: specific maximums (e.g., max 20 electronic transformers) may restrict some lighting setups.
  • No IP protection for wet locations (IP20) — limited to dry indoor installations.
M: OA-GPT-5-NAN

Product Specification

Type

Actuator

Standard

KNX

Function

Switching actuator (on/off), On/Off delay

Topology

Bus

Special features

IP20

M: OA-GPT-54-NAN

Product Description

MDT Switching Actuator AKS 10A Manual

The MDT Switching Actuator AKS 10A is a compact, DIN-rail mounted KNX switching actuator built to control lighting and other electrical loads in modern installations. Available in 2, 4, 8 and 12-output versions, the AKS 10A combines high channel density with robust switching capability. Each channel is driven by a bistable relay, enabling the actuator to retain its output state during KNX bus power interruptions. Manual push buttons and green status LEDs on each channel provide immediate local control and visual confirmation of states.

Designed for professional electricians, the AKS 10A supports a range of load types — from incandescent and halogen lamps to fluorescent fixtures and electronic transformers — with defined maximums per channel and overall device current limits (20 A, 40 A, 80 A, 120 A depending on model). It handles inrush currents of up to 600 A for brief pulses and accommodates capacitive loads up to 140 µF. KNX integration is seamless via a TP-256 interface with long frame support and compatibility with ETS4/5 application software.

Installation is straightforward: clip the unit onto a 35 mm DIN rail, connect the KNX bus and load wiring, protect outputs with upstream circuit breakers, and set the device’s physical address and parameters in ETS. The programming button and red programming LED facilitate commissioning; the red LED extinguishes after successful programming. All screw terminals are touch-protected behind the enclosure and the device is intended for dry indoor installation.

Functionally rich, the AKS 10A allows per-channel parameterization in ETS to enable logical links, status feedback, locking functions, central switching, timed delays, staircase lighting timers and scene control. After bus voltage loss or return the relays either retain their last known state or follow individually configured recovery behaviors. The actuator’s low KNX bus consumption and small footprint reduce distribution costs and simplify installations.

For safe operation, the unit must be installed and serviced only by qualified electricians in accordance with local regulations and KNX guidelines. Outputs can be live after mains application or when controlled by KNX telegrams, so always isolate upstream power before maintenance. The device carries CE marking and is approved for EU use only.

Notes:

  • Models: AKS-0210.03, AKS-0410.03, AKS-0810.03, AKS-1210.03.
  • Max per-channel switching: 10 A at 230 VAC; specific lamp-type limits apply.
  • Commissioning requires ETS and MDT application software (download from MDT website).
  • Intended for fixed installation on DIN 35 mm rail in dry indoor environments.