MDT AKI 16/20A Manual

0.0 · 0 Ratings

PDF manual · 2 Pages

English

M: QW-35-FL
page

/ 2

Loading...
31b7bff487043412a55e57c80a58cc7b9814 page 1
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: + 49 - 2263 - 880
•
Fax: + 49 - 2263 - 4588
•
•
www.mdt.de
Stand: 0520
Allgemeine Sicherheitshinweise - Important safety notes Lebensgefahr durch elektrischen Strom - Danger High Voltage
Das Gerät darf nur von Elektrofachkräften montiert und angeschlossen werden. Beachten sie die länderspezischen •
Vorschriften sowie die gültigen KNX-Richtlinien. Die Geräte sind für den Betrieb in der EU zugelassen und tragen das CE
Zeichen. Die Verwendung in den USA und Kanada ist nicht gestattet. Installation and commissioning of the device
only be carried out by authorised electricans. The relevant standards, directives, regulations and instructions must be
observed. The devices are approved for use in the EU and have the CE mark. Use in USA and Canada is prohibited.
Nach dem Einbau des Gerätes und Zuschalten der Netzspannung kann an den Ausgängen Spannung anliegen. •
Über die eingebauten Kanaltaster lassen sich die Ausgänge ausschalten. After Installation and connecting mains power
supply the outputs can be alive. The outputs can be switched OFF by using the push buttons on top of the device.
In eingebauten Zustand kann ein KNX-Bustelegramm die Ausgänge jederzeit spannungsführend schalten. •
After installation a KNX bus telegram can switch the outputs alive.
Vor Arbeitsbeginn am Gerät immer über die vorgeschalteten Sicherungen spannungsfrei schalten. •
Disconnect the mains power supply prior to installation or disassembly.
Alle spannungsführenden Klemmen und Anschlüsse müssen nach der Installation vollständig durch die Schalttafel-•
abdeckung berührungssicher verschlossen werden. Die Schalttafelabdeckung darf nicht ohne Werkzeug zu öffnen sein.
All screw terminals and connections under current must be covered completely against touching by the switch panel.
It should not be possible to open the switch panel cover without using tools.
Anschlußklemmen, Bedien- und Anzeigeelemente Schaltakor AKI
Terminals, Operating and Display Switch Actuator AKI
Technische Daten
Technical Data
AKI-0416.04 AKI-0816.04 AKI-1216.04
Anzahl Ausgänge
Number of outputs
4 8 12
Maximale Schaltleistung je Kanal
Output switching ratings
Ohmsche Last
Ohmic load
16A/20A* 16A/20A* 16A/20A*
Kapazitive Last
Capacative load
200µF 200µF 200µF
Spannung
Voltage
230VAC 230VAC 230VAC
Maximaler Einschaltstrom
Maximum inrush current
600A/150µs
300A/600µs
600A/150µs
300A/600µs
600A/150µs
300A/600µs
Maximale Last
Maximum lamp loads
Glühlampen
Incandescent lamps
3680W 3680W 3680W
HV- Halogenlampen
Halogen lamp 230V
3680W 3680W 3680W
NV- Halogenlampen
Halogen lamp, electronic transformer
2000W 2000W 2000W
Leuchtstofampen unkompensiert
Fluorescent lamp not compensated
3680W 3680W 3680W
Leuchtstofampen parallelkompensiert
Fluorescent lamp parallel compensated
2500W 2500W 2500W
max. Anzahl EVG (elektronischer Trafo)
max. number of electronic transformers
28 28 28
mech. Schalthäugkeit
Output life expectancy (mech.)
1.000.000 1.000.000 1.000.000
Spezikation KNX Schnittstelle
Specication KNX interface
TP-256 mit Long Frame Unterstützung für ETS5
TP-256 with long frame support for ETS5
Verfügbare KNX Datenbanken
Available application software
ETS 4/5 ETS 4/5 ETS 4/5
Max. Kabelquerschnitt
Permitted wire gauge
Schraubklemmen
Screw terminal
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
1 x (0,5 - 4,0mm²)
2 x (0,5 - 2,5mm²)
KNX Busklemme
KNX busconnection terminal
0,8mm Ø, solid core 0,8mm Ø, solid core 0,8mm Ø, solid core
Anzugsmoment Schraubklemme
Torque screw terminal
0,5Nm 0,5Nm 0,5Nm
Versorgungsspannung
Power Supply
KNX Bus KNX Bus KNX Bus
Leistungsaufnahme KNX Bus typ
Power consumption KNX bus typ.
< 0,25W < 0,25W < 0,25W
Umgebungstemperatur
Operation temperature range
0 bis + 45°C 0 bis + 45°C 0 bis + 45°C
Schutzart
Enclosure
IP 20 IP 20 IP 20
Abmessungen (Teilungseinheiten)
Dimensions MDRC (Space Units)
4TE 8TE 12TE
Technische Daten Schaltaktor AKI - Technical Data Switch Actuator AKI
* Summenstrombelastbarkeit benachbarter Ausgänge max.32A * total current carrying capacity neighbouring outputs max. 32A
** gilt für NV- Halogenlampen mit elektronischem Transformator ** low voltage halogen lamps with electronic transformer
1
2 3
4
5
AKI-0416.04 AKI-0816.04
1
2 3
4 4
5
Betriebsanleitung Schaltaktor AKI - nur für autorisiertes Elektrofachpersonal
Operating Instructions Switch Actuator AKI - for authorised electricans
1 - Busanschlußklemme
- KNX busconnection terminal
2 - Programmiertaster
- Programming key
3 - Rote Programmier LED
- Red programming LED
4 - Anschlußklemmen
- Output power terminal
5 - Handbetätigung / Status
- Manual actuation / Status

Chat with your MDT AKI 16/20A manual using AI

Get instant AI answers from your MDT AKI 16/20A manual

Ask anything about the MDT AKI 16/20A. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend AKI 16/20A?

Yes No

Frequently Asked Questions

A

The device supports a maximum switching current of 16A or 20A depending on the load type, with a total neighboring output capacity limited to 32A.

Is this answer helpful?

A

Yes, each channel has a mechanical push button allowing manual switching even if the KNX bus is inactive or during troubleshooting.

Is this answer helpful?

A

No, the device is rated IP20 and must be installed only in dry indoor rooms within distribution boards or closed boxes.

Is this answer helpful?

A

This specific model focuses on switching loads using bistable relays and does not natively support analog dimming without additional components.

Is this answer helpful?

A

Use ETS 4 or ETS 5 software to assign physical addresses and configure parameters, then upload the data by pressing the programming key on the unit.

Is this answer helpful?

A

All relays retain their current switching position until power is restored, preventing unexpected changes in lighting or appliance states.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Handles extreme inrush currents suitable for heavy C-loads
  • Bistable relays hold position during power failures
  • Supports up to 12 independent channels per unit
  • Includes manual push-button operation for direct control
  • Fully compatible with ETS 4 and ETS 5 software
VS

Disadvantages

  • Requires professional installation by authorized electricians
  • Not approved for use in USA and Canada markets
  • Limited to dry indoor environments only
  • No IP rating beyond basic protection against solid objects
  • Fixed installation requires DIN rail mounting space
M: QW-35-FL

Product Specification

Type

Actor

Standard

KNX

Function

Switch actuator (on/off), On/Off delay

Topology

Bus

Features

IP20

M: QW-35-FL

Product Description

MDT Switch Actuator AKI 16/20A: The Ultimate Control Solution

The MDT Switch Actuator AKI 16/20A represents a pinnacle of modern building automation technology, designed to seamlessly integrate into KNX systems for efficient and reliable control of electrical loads. This robust device serves as the backbone for managing lighting, heating, and other electrical appliances in residential and commercial environments. By receiving KNX telegrams, it can independently switch up to twelve different loads, offering unparalleled flexibility for complex installation needs.

Engineered with bistable relays, this actuator ensures that every output remains stable even during power fluctuations. The mechanical manual actuation feature allows users to control lights directly from the device itself, providing immediate status visibility through dedicated indicators. Whether handling incandescent lamps, halogen lights, or fluorescent fixtures, the AKI series is built to withstand extreme inrush currents, making it ideal for heavy-duty applications often labeled as C-loads.

Installation is straightforward for authorized electricians, as the unit mounts securely on standard DIN 35mm rails within distribution boards. Each channel features separate terminals, simplifying wiring and enhancing safety. The device supports extensive programming via ETS software, enabling logical operations, scene settings, time delays, and staircase lighting functions. In the event of a mains voltage failure, the relays maintain their last position, ensuring continuity of operation. Furthermore, the system allows for individual configuration of relay states following bus voltage recovery, tailoring behavior to specific user requirements.

With a compact design and high switching capacity, the MDT Switch Actuator AKI 16/20A stands out as a versatile tool for professionals seeking precision and reliability in KNX installations. Its ability to handle capacitive loads and electronic transformers further expands its utility across diverse electrical scenarios.

Important Notes

  • Always disconnect mains power before installation.
  • Ensure all screw terminals are covered after wiring.
  • Use only authorized electricians for mounting.
  • Download application software from the official MDT website prior to commissioning.