MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: + 49 - 2263 - 880
•
Fax: + 49 - 2263 - 4588
•
•
www.mdt.de
Stand: 0621
Technische Änderungen und Irrtümer vorbehalten,
Abbildungen können abweichen.
Technische Daten
Technical Data
AKH-0400.03
AKH-0600.03
AKH-0800.03
Anzahl Ausgänge
Number of outputs
4/6/8
Maximale Schaltleistung
Output switching current
bei 24VAC und ohmscher Last
24VAC and ohmic load
500mA
bei 230VAC und ohmscher Last
230VAC and ohmic load
500mA
max. Einschaltstrom**
max. inrush current**
5A
Externe Schaltspannung
External switching voltage
24-230VAC
Maximale Last
Maximum load
Anzahl elektrothermische Stellantriebe*
Number of electrothermic valves*
230VAC: 4 per Kanal
24VAC: 3 per Kanal
Mech. Schalthäugkeit
Output life expectancy
Triacausgang, verschleißfrei
Triac output, wearless
Spezikation KNX Schnittstelle
Specication KNX interface
TP-256 mit Long Frame Unterstützung für ETS5
TP-256 with long frame support for ETS5
Verfügbare KNX Datenbanken
Available application software
ETS 5
Max. Kabelquerschnitt
Permitted wire gauge
Schraubklemmen (max. 0,5Nm Anzugsmoment)
Screw terminal (max. 0,5Nm tightening torque)
0,5 - 4,0mm² solid core
0,5 - 2,5mm² nely stranded
KNX Busklemme
KNX busconnection terminal
0,8mm Ø, solid core
Versorgungsspannung
Power Supply
KNX Bus
Leistungsaufnahme KNX Bus typ.
Power consumption KNX bus typ.
< 0,3W
Umgebungstemperatur
Operation temperature range
0 bis + 45°C
Schutzart
Enclosure
IP 20
Abmessungen REG (Teilungseinheiten)
Dimensions MDRC (Space Units)
2/3/4TE
Technische Daten Heizungsaktor AKH - Technical Data Heizungsaktor Actuator AKH
1
1
2
2
3
3
4
4
5 5
AKH-0400.03 AKH-0600.03
Allgemeine Sicherheitshinweise - Important safety notes Lebensgefahr durch elektrischen Strom - Danger High Voltage
• Das Gerät darf nur von Elektrofachkräften montiert und angeschlossen werden. Beachten sie die länderspezischen
Vorschriften sowie die gültigen KNX-Richtlinien. Die Geräte sind für den Betrieb in der EU zugelassen und tragen das CE
Zeichen. Die Verwendung in den USA und Kanada ist nicht gestattet.
Installation and commissioning of the device only be carried out by authorised electricans. The relevant standards,
directives, regulations and instructions must be observed. The devices are approved for use in the EU and have the CE
mark. Use in USA and Canada is prohibited.
• Nach dem Einbau des Gerätes und Zuschalten der Netzspannung kann an den Ausgängen Spannung anliegen.
After Installation and connecting mains power supply the outputs can be alive.
• In eingebauten Zustand kann ein KNX-Bustelegramm die Ausgänge jederzeit spannungsführend schalten.
After installation a KNX bus telegram can switch the outputs alive.
• Vor Arbeitsbeginn am Gerät immer über die vorgeschalteten Sicherungen spannungsfrei schalten.
Disconnect the mains power supply prior to installation or disassembly.
• Alle spannungsführenden Klemmen und Anschlüsse müssen nach der Installation vollständig durch die Schalttafel-
abdeckung berührungssicher verschlossen werden. Die Schalttafelabdeckung darf nicht ohne Werkzeug zu öffnen sein.
All screw terminals and connections under current must be covered completely against touching by the switch panel.
It should not be possible to open the switch panel cover without using tools.
Anschlussklemmen, Bedien- und Anzeigeelemente Heizungsaktor AKH
Terminals, Operating and Display Heating Actuator AKH
Betriebsanleitung Heizungsaktor AKH - nur für autorisiertes Elektrofachpersonal
Operating Instructions Heating Actuator AKH - for authorised electricans
1 - Busanschlussklemme
- KNX busconnection terminal
2 - Programmiertaster
- Programming key
3 - Rote Programmier LED
- Red programming LED
4 - Anschlussklemmen
- Output power terminal
5 - Grüne Status LED
- Green status LED
* je nach Hersteller. Einschaltstrom bei 4 Stellantrieben muß < 1A je Stellantrieb sein
** je 4er Gruppe (AKH-0400.03 und AKH-0800.3) oder 3er Gruppe (AKH-0600.03)
* depends on manufactorer. Inrush current for 4 electrothermic valves has to be < 1A each electrothermic valve
** every group of four outputs (AKH-0400.03 and AKH-0800.3) or every group of three outputs (AKH-0600.03)
2
3
4
5
AKH-0800.03
1
®

Chat with your MDT AKH manual using AI

Get instant AI answers from your MDT AKH manual

Ask anything about the MDT AKH. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend AKH?

Yes No

Frequently Asked Questions

A

It controls electrothermic valve drives for heating and cooling systems within a KNX network, offering integrated temperature regulation and energy optimization.

Is this answer helpful?

A

No, you must select either 24VAC or 230VAC for the entire unit. Mixing these voltages is not allowed and will result in errors.

Is this answer helpful?

A

It switches off circulation pumps when all valves are closed and uses automatic summer/winter modes to adjust operation based on outdoor conditions.

Is this answer helpful?

A

If connected to a window contact, the actuator locks heating and switches to frost protection mode until the window is closed again.

Is this answer helpful?

A

Yes, it supports underfloor heating with specific PWM cycle settings and minimum flow temperature limitations to protect floor coverings.

Is this answer helpful?

A

The device sends plain text diagnosis messages and flashes LEDs in specific patterns to indicate errors like short circuits or missing signals.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Integrated PI controller reduces hardware costs by eliminating the need for external room controllers
  • Automatic pump shutdown feature significantly lowers energy consumption during idle periods
  • Plain text diagnosis simplifies commissioning and maintenance for system integrators
  • Flexible control modes support both fast radiator systems and slow underfloor heating
  • Sticking protection prevents valve seizure by cycling them every six days
VS

Disadvantages

  • Mixing 24VAC and 230VAC power sources on one unit is not permitted and causes faults
  • Complex configuration may require detailed knowledge of ETS parameter settings
  • Dew point alarm functionality is limited to cooling mode operation only
  • Emergency mode relies on cyclical control value pulses which must be maintained
  • Initial setup requires careful attention to phase wiring for multi-channel models
M: QW-35-FL

Product Specification

Type

Actor

Standard

KNX

Function

Heating control

Topology

Bus

M: QW-35-FL

Product Description

MDT Heating Actuator AKH: Advanced Climate Control

The MDT Heating Actuator AKH series represents a significant leap in KNX-based climate management, designed to bring precision and flexibility to modern heating and cooling systems. Whether managing a small apartment or a large commercial building, these actuators offer robust control over electrothermic valve drives with options for 4, 6, or 8 channels depending on the specific model. The device supports both 24VAC and 230VAC power supplies, ensuring compatibility with a wide range of existing infrastructure without compromising performance.

One of the standout features of the MDT Heating Actuator AKH is its integrated PI temperature controller. This allows for sophisticated room temperature regulation using only setpoints and current temperature readings, eliminating the need for separate external controllers in many scenarios. The system intelligently handles both continuous and two-point control modes, adapting seamlessly to different types of heating elements like radiators or underfloor systems. Users can configure minimum flow temperatures to prevent cold floors in transitional seasons, enhancing comfort while maintaining energy efficiency.

Energy optimization is at the core of the design. The actuator includes logic to automatically switch off circulation pumps when no heat demand exists, significantly reducing energy waste during summer months or transition periods. It also features an automatic summer/winter switchover based on outdoor temperature, time, and date, ensuring the system operates in the most appropriate mode without manual intervention. Additional safety mechanisms include window contact integration, which blocks heating if a window is open, and a sticking protection function that periodically cycles valves to prevent them from seizing.

Commissioning is streamlined through extensive diagnostic capabilities. The unit provides plain text status reports via communication objects, allowing installers to quickly identify issues such as short circuits, missing control values, or dew point alarms. The LED indicators on each channel provide immediate visual feedback on the operational state, including emergency modes and fault conditions. With support for long frame telegrams, programming time is reduced, and the ability to update firmware via the MDT Update Tool ensures the device remains compatible with future standards.

Key Highlights

  • Integrated PI controller for precise temperature management.
  • Automatic pump shutdown for energy savings.
  • Comprehensive diagnostic text output for easy troubleshooting.
  • Support for both switching and continuous control modes.
  • Flexible voltage options for diverse installation needs.

Notes

Always ensure that the actuator is powered by either 24VAC or 230VAC exclusively; mixing voltages on a single unit is strictly prohibited. When configuring multiple channels, remember that specific phase connections are required depending on the model variant to avoid fault states.