Manual.ly Logo

Hager TYA606E Manual

0.0 · 0 Ratings

PDF manual · 4 Pages

English

M: QW-35-FL
page

/ 4

Loading...
48adb2d3917c664b5947f78fbb6d6062155f page 1
Bus
auto
L3
L2
L1
N
C2
C1
C4C4
C3C3
C6C6
C5C5
TYA606E
C1 C2
2
4
C3 C4
6
8
C5 C6
10
12
1
3
C1 C2
5
7
C3 C4
9
11
C5 C6
1 • Commutateur Auto/Manu
• Schalter Auto/Manu
• Auto/Manu switch
2 • Voyants d’état
• Kontrollleuchten
• Indicators state
3 • Boutons poussoirs de commande
locale
• Taster zur lokalen Ansteuerung
• Local command push-button
4 • Bouton poussoir lumineux
d’adressage physique
• Leuchttaster zur physikalischen
Adressierung
• Physical addressing lighted push
button
Les sorties peuvent être raccordées sur des phases di érentes.
Die Schaltausgänge können an unterschiedliche Phasen angeschlossen werden.
The outputs can be connected to di erent phases.
1
4
2
3
Type de charges / Lasttyp / Load type
230 Vv
Lampes à incandescence
Glhlampen
Incandescent lamps
2300 W
230 Vv
Lampes halogènes
Halogenlampen
Halogen lamps
2300 W
12V v
24V
s
Transformateur ferromagnétique
Konventioneller Transformator
Conventional transformer
1600 W
12V s
24V s
Transformateur électronique
Elekronischer Transformator
Electronic transformer
1380 W
230 Vv
Tubes fluorescents non compensés
Leuchstofflampen ohne Vorschaltgerät
Fluorescent tubes non compensated
800 W
Tubes fluorescents pour ballast électronique (mono ou duo)
Leuchstofflampen mit EVG (mono oder duo)
Fluorescent tubes for electronic ballast (mono or duo)
25 x 18 W
Tubes fluorescents compensés en parallèle
Leuchstofflampen mit konventionellen Vorschaltgerät, Parallelschaltung
Parallel compensated fluorescent tubes
1000 W
130 µF
230 Vv
Fluo compact
Sparlampen
Compact fluorescent
25 x 18 W
LED
230 Vv
LED 200 W
:.,nB
tebis
A Attention!
• Appareil à installer uniquement par un
installateur électricien selon les normes
d’installation en vigueur dans le pays.
• Respecter les règles d’installation TBTS.
• Ne pas dépasser la charge maximale
admissible par appareil
• Le non-respect de ces instructions peut
entraîner des dommages sur l'appareil,
un incendie ou d'autres conséquences
dangereuses.
E Achtung!
• Einbau und Montage drfen nur durch
eine Elektrofachkraft gemäß den
einschlägigen Installationsnormen des
Landes erfolgen.
• Installationsvorschriften zur
Schutzmaßnahme SELV beachten.
• Die zulässige Höchstlast pro Gerät darf
nicht berschritten werden.
• Die Nichteinhaltung dieser Anweisungen
kann Schäden am Gerät, Brände oder
sonstige gefährliche Folgen verursachen.
Z Caution!
• This device is to be installed only by a
professional electrician  tter according
to local applicable installation standards.
• Conform to SELV installation rules.
• Do not exceed the maximum permissible
load per device.
• Failure to follow these instructions may
cause damage to the device,  re or other
dangerous consequences.
TYA606E
i a
Module 6 sorties avec mesure de courant
y e
Schaltausgang 6-fach mit Stromerkennung
r z
Output module 6-fold with current monitoringa
1 6LE004131A
6LE004131A

Chat with your Hager TYA606E manual using AI

Get instant AI answers from your Hager TYA606E manual

Ask anything about the Hager TYA606E. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend TYA606E?

Yes No

Frequently Asked Questions

A

Each of the six channels can handle up to 16A at 230V AC1. However, the sum of all currents across all six channels must not exceed 68A to ensure safe operation.

Is this answer helpful?

A

Yes, you can control the outputs manually using the local push-buttons when the Auto/Manu switch is set to Manual position. In Auto mode, only KNX bus commands are accepted.

Is this answer helpful?

A

Yes, the actuator supports various LED loads up to 200W per channel at 230V. It also handles fluorescent tubes with electronic ballasts and conventional transformers effectively.

Is this answer helpful?

A

Configuration is done using ETS application software. You must set the switch to Auto mode to download parameters. Physical addressing is performed using the lighted push-button.

Is this answer helpful?

A

If incompatible application software is loaded, the state indicators will continuously flicker after powering on or downloading. This indicates a configuration error that needs correction.

Is this answer helpful?

A

Installation requires mounting on a DIN rail and connecting wires between 0.75mm² and 2.5mm². Due to safety regulations, only qualified electricians should perform the installation.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Six independent channels allow versatile control of multiple electrical loads simultaneously
  • Integrated current detection enables real-time energy monitoring and fault identification
  • Manual override capability provides local control even during network outages
  • Compact 6TE design saves space in distribution boards while maintaining high capacity
  • Visual status LEDs offer instant feedback on relay states and bus connectivity
VS

Disadvantages

  • Requires professional installation by a qualified electrician due to high voltage risks
  • Maximum total current limit of 68A restricts usage in very high-load industrial applications
  • Local buttons become inactive in Auto mode limiting manual access without reconfiguration
  • No built-in surge protection beyond standard category III limits
  • Configuration requires specific ETS software knowledge which may have a learning curve
M: QW-35-FL

Product Specification

Type

Actor

Standard

KNX

Function

Switch actor (on/off)

Topology

Bus

Features

IP20, IP30, IK04

M: QW-35-FL

Product Description

Hager KNX Switch Actuator 6/3-fold 16A C-Load with Current Detection

The Hager KNX Switch Actuator TYA606E is a robust solution for modern building automation systems, designed to seamlessly integrate electrical loads with the KNX bus. This 6-fold actuator features current detection capabilities, allowing for advanced monitoring and control of lighting and other electrical devices. With a compact 6TE width, it fits perfectly into standard DIN rail installations while offering powerful functionality.

This device supports six independent channels that can be controlled via the KNX bus or manually using local push-buttons when set to manual mode. The integrated state indicators provide immediate visual feedback on relay status, ensuring easy troubleshooting. The unit includes a physical addressing button for quick configuration and bus verification. It handles various load types including incandescent lamps, halogen lamps, electronic transformers, and LED systems, with a maximum switching capacity of 16A per channel.

Safety is paramount, as the device must be installed by qualified electricians adhering to SELV rules. The current monitoring function enables efficient energy visualization, threshold surveillance, and fault detection for wiring issues. Whether managing lighting in residential settings or complex commercial environments, this actuator delivers reliable performance with precise measurement accuracy within a 0.05A to 16A range.

Key Features

The actuator operates on a 30V SELV supply voltage and consumes minimal power on the KNX bus. Its design ensures compatibility with ETS application software for lighting and shutter configurations. Users can switch between automatic bus control and local manual operation effortlessly. The device withstands harsh environmental conditions with an operating temperature range from -5°C to +45°C and offers IP20 protection for indoor use.

Important Notes

Always ensure the total current across all six channels does not exceed 68A. Do not exceed the maximum permissible load per device to prevent damage or fire hazards. Regular maintenance and adherence to local installation standards are crucial for optimal safety and longevity.