Manual.ly Logo

Growatt MOD TL3-X Manual

0.0 · 0 Ratings

PDF manual · 31 Pages

English

M: QW-35-FL
page

/ 31

Loading...
6e40de7505f5f6f28b1a7db697ccb0ad9d59 page 16
38
37
Don't disconnect the DC connector while the inverter is connected to the
grid.
Before turning the inverter on, please make sure the PV input voltage and current are
within the MPPT limits.
Follow the steps below to turn the inverter on:
1.Pull the PV and AC cable make sure there is no loose or shaking.
2.Make sure the cable polarity is correct and voltage is less than 1100V
3.Switch on the build-in DC isolator at the bottom of the inverter.
4.Switch on the PV Array and DC isolator next to your inverter, if you can not find this
switch, skip this step.
5.Switch on the Solar AC isolator if the inverter is more than 3 meters away from your
switchboard.
6.Switch on the solar supply main switch in the switch board.
12.1 Start the inverter
12.2 Shut down the inverter
Steps to turn off the inverter:
1. Disconnect the AC circuit breaker to prevent the inverter from starting again;
2. Turn off the DC switch;
3. Check the operating status of the inverter;
4. Wait until the LED and OLED display are off, indicating that the inverter is turned off.
Danger
12 Start and shut down the inverter
Troubleshooting 13
13.1 Error message
13.2 System error
When a malfunction occurs, an error message will be displayed on the OLED screen and
the LED indicator red will light up. Faults include system faults and inverter faults.
In some cases, you may be advised to contact Growatt, please provide the following
information.
Information about the inverter::
●Serial number
●Model
●Error message on OLED
●A short description of the problem
●Grid voltage
●DC input voltage
●Can you reproduce the failure? If so, how?
●Has this problem occurred in the past?
●What were the environmental conditions when the problem occurred?
Information about photovoltaic panels:
●PV panel manufacturer's name and model
●Panel output power
●Voc of the panel
●Vmp of the panel
●Imp of the panel
●The number of panels in each string
●If you need to replace the device, please ship it to the original box.
Warning Code
Warning
message
Description
Suggest
Warning 200
String fault
1.After shutdown,Check the panel is normal.
2.If error message still exists, contact manufacturer.
Warning 201
String PID quick connect
terminal detection error
1.After shutdown,Check the string terminal wiring.
2. If the error message still exists, contact the
manufacturer.
Warning 202
D C S P D f u n c t i o n
abnormal
1.After shutdown,Check the DC SPD.
2.If error message still exists,contact manufacturer.
Warning 203
PV Circuit short
1.Check the PV1 or PV2 wiring is short-circuited
2.If error message still exists,contact manufacturer.
Warning 204
Dry contact function
abnormal
1.After shutdown,Check the dry Dry contact wiring.
2 . I f t h e e r r o r me s s a g e s t i l l e x i s t s , c o n t a c t
manufacturer.
Warning 205
PV Boost driver broken
1.Restart inverter.
2.If error message still exists,contact manufacturer.
Warning 206
A C S P D f u n c t i o n
abnormal
1.After shutdown,Check the AC SPD.
2.If error message still exists,contact manufacturer.
11 Maintenance and Cleaning
11.1 Checking Heat Dissipation
11.2 Cleaning the Inverter
11.3 Checking the DC Disconnect
If the inverter regularly reduces its output power due to high temperature, please
improve the heat dissipation condition. Maybe you need to clean the heat sink.
If the inverter is dirty, turn-off the AC breaker and DC switch ,waiting the inverter shut
down ,then clean the enclosure lid, the display, and the LEDs using only a wet cloth. Do
not use any cleaning agents (e.g. solvents or abrasives).
Check for externally visible damage and discoloration of the DC Disconnect and the
cables at regular intervals.If there is any visible damage to the DC Disconnect, or visible
discoloration or damage to the cables, contact the installer.
Ø Once a year, turn the rotary switch of the DC Disconnect from the On position to the
Off position 5 times in succession. This cleans the contacts of the rotary switch and
prolongs the electrical endurance of the DC Disconnect.

Chat with your Growatt MOD TL3-X manual using AI

Get instant AI answers from your Growatt MOD TL3-X manual

Ask anything about the Growatt MOD TL3-X. Answers come from this manual, with the pages they are based on.

MOD TL3-X Maintenance Schedule

Remind me when maintenance is due
Yearly
Cycle the DC disconnect rotary switch

Once a year, turn the rotary switch from On to Off position 5 times in succession to clean contacts and prolong electrical endurance.

Show in the manual (page 22)
As needed
Clean the heat sink if output drops due to high temperature

If the inverter regularly reduces its output power due to high temperature, improve heat dissipation by cleaning the heat sink.

Show in the manual (page 22)
As needed
Clean the inverter enclosure and display

Turn off AC breaker and DC switch, wait for shutdown, then clean the lid, display, and LEDs with a wet cloth. Do not use solvents or abrasives.

Show in the manual (page 22)
Regularly
Check DC disconnect and cables for damage

Inspect for externally visible damage or discoloration of the DC Disconnect and cables at regular intervals. Contact installer if issues are found.

Show in the manual (page 22)

Free maintenance reminders

Timed to your purchase date. Always free, unsubscribe anytime.

By submitting you agree to the privacy policy. Unsubscribe with one click in any email.
M: qwen/qwen3.8-flash

Ask a Question

0/1000

Do you recommend MOD TL3-X?

Yes No

Frequently Asked Questions

A

The maximum DC input voltage for the Growatt MOD TL3-X series is 1100V. It is crucial to ensure that the open-circuit voltage of your PV string does not exceed this limit under any operating conditions to prevent damage to the inverter.

Is this answer helpful?

A

Yes, the inverter has an IP66 protection rating, making it suitable for both indoor and outdoor installation. However, it should be placed in a sheltered location to avoid direct exposure to strong sunlight and heavy rain to prevent overheating and maintain optimal performance.

Is this answer helpful?

A

Yes, the MOD TL3-X includes integrated export limitation functionality. You can connect a Growatt smart meter, CT, or use a ripple control signal receiver to manage power export according to local grid regulations.

Is this answer helpful?

A

For most errors, you can restart the inverter by turning the DC switch and AC circuit breaker off, waiting for the internal components to discharge, and then turning them back on. If the error persists, check the specific fault code and contact technical support.

Is this answer helpful?

A

No, the Arc-Fault Circuit Interrupter (AFCI) is an optional feature. While some models include it, others require a specific configuration or additional module to enable arc detection and interruption capabilities.

Is this answer helpful?

A

If the leakage current exceeds 300mA for more than 300ms, the inverter will report a fault code, typically Error 201, and stop generating power to ensure safety. You must investigate the source of the leakage before restarting the system.

Is this answer helpful?

A

You should regularly check the inverter for dust and dirt. If the heat sink appears dirty, turn off the power and clean the enclosure with a wet cloth. Avoid using solvents or abrasives to prevent damage to the surface.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Dual independent MPPT trackers optimize energy harvest across different panel orientations
  • High peak efficiency of up to 98.6% maximizes energy conversion
  • IP66 protection rating ensures durability in harsh outdoor conditions
  • Integrated OLED display and touch buttons provide easy user interaction
  • Supports multiple communication protocols including Wi-Fi and 4G for remote monitoring
VS

Disadvantages

  • Requires professional installation by certified electricians due to high voltage risks
  • Some advanced monitoring modules are sold separately as optional extras
  • Transformerless design requires strict adherence to grounding rules to avoid errors
  • Direct sunlight exposure may cause overheating and power derating without shading
  • AFCI protection is an optional feature not included in all standard configurations
M: QW-35-FL

Product Specification

Note

Prices include partially 0% VAT rates for AT and DE

Type

Solar inverter, without transformer, passive

Input voltage

140-1100V DC

Max input current

13A

MPP voltage range

140-1000V DC

Number of MPP trackers

2

Output phases

3-phase

Input connector

MC4

Protection class

IP66

Ambient temperature

-13F to 140F

M: QW-35-FL

Product Description

Discover the Growatt MOD TL3-X Series Inverter

The Growatt MOD TL3-X series represents a significant leap in photovoltaic technology, designed to maximize energy harvest while ensuring robust reliability for residential and commercial solar installations. This transformerless inverter efficiently converts direct current from solar panels into alternating current suitable for grid connection, supporting both single-phase and three-phase systems depending on the model selected. With a sleek design and an IP66 protection rating, the unit is built to withstand harsh outdoor environments, operating reliably within a temperature range of -25°C to +60°C.

At the heart of the MOD TL3-X lies its advanced dual independent maximum power point tracking (MPPT) system. This feature allows the inverter to manage two separate strings of solar panels independently, optimizing energy production even when panels are partially shaded or oriented differently. The high efficiency rating, reaching up to 98.6%, ensures that minimal energy is lost during conversion, translating directly to higher savings for the user. The device features a user-friendly OLED display combined with LED indicators, providing real-time status updates and easy access to operational data through intuitive touch buttons.

Installation is streamlined for professional electricians, with clear guidelines for wall mounting and wiring. The inverter supports flexible communication options including RS485, USB, and optional modules for Wi-Fi, GPRS, and 4G connectivity, enabling seamless integration with monitoring systems. Safety is paramount, with integrated features like residual current monitoring, anti-islanding protection, and optional Arc-Fault Circuit Interrupter (AFCI) capabilities to prevent fire hazards. Whether you are upgrading an existing system or installing a new array, the Growatt MOD TL3-X offers a powerful, efficient, and safe solution for modern solar energy needs.

M: QW-35-FL

© Copyright 2026 Manual.ly