Manual.ly Logo

Eltako FHK61U-230V Manual

0.0 · 0 Ratings

PDF manual · 2 Pages

English

M: gpt-5.6-terra
page

/ 2

Loading...
507c852486b461260f68ab5a791dde09666a page 1
1 NO contact potential free 10A/250V AC.
Only 0.8 watt standby loss. Encrypted
wireless, bidirectional wireless and
repeater function are switchable.
For installation.
45mm long, 45mm wide, 33mm deep.
Supply voltage 230V.
If a power failure occurs, the switching
state is retained. If a power failure occurs
repeatedly, the device is switched off in a
defined sequence.
After installation, wait for short automatic
synchronisation before the switched
consumer is connected to the mains.
This heating/cooling relay evaluates the
information from wireless temperature
controllers or sensors. Possibly supple-
mented by window/door contacts, motion
detector, Hoppe window handles and
wireless pushbuttons.
Starting in production week 11/14, you
can teach in encrypted sensors. You
can switch on bidirectional wireless
and/or a repeater function.
Every change in state of the contact is
confirmed by a wireless telegram. This
wireless telegram can be taught-in into
other actuators and the GFVS software.
Especially into a FSR61 to synchronously
switch a heat circulating pump with the
valves.
GB
Only skilled electricians may install
this electrical equipment otherwise
there is the risk of fire or electric
shock!
Temperature at mounting location:
-20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity:
annual average value <75%.
Wireless actuator
Heating/cooling relay
FHK61U-230V
30 100 050 - 2
valid for devices from production week
11/14 (see bottom side of housing)
Function rotary switches
Top rotary switch for operating modes:
H1: Heating operation with PWM control
at T = 4 minutes. (suitable for valves
with thermoelectric valve drive)
H2: Heating operation with PWM control
at T = 15 minutes. (suitable for valves
with motor-driven valve drive)
H3: Heating operation with 2-point
control.
K1: Cooling operation with PWM control
at T = 15 minutes.
K2: Cooling mode with 2-point control.
Switchover is visualised by LEDs flashing.
Bottom rotary switch for adjustable
hysteresis and PWM influence:
Left stop: lowest hysteresis 0.5°.
Middle position: hysteresis 2.5°.
Right stop: largest hysteresis 4.5°.
Inbetween, divisions in steps of 0.5°
visualised by LEDs flashing.
Two-point control mode:
The hysteresis rotary switch sets the
required difference between the switch-on
and switch-off temperatures.
When the 'actual temperature >= reference
temperature', the device is switched off.
When the 'actual temperature <=
(reference temperature - hysteresis)', the
device is switched on. The signs are the
opposite in cooling mode.
PWM control mode:
The hysteresis rotary switch set the required
temperature difference at which the device
is switched on at 100%. When the 'actual
temperature >= reference temperature',
the device is switched off.
When the 'actual temperature <=
(reference temperature - hysteresis)', the
device is switched on at 100%.
If the 'actual temperature' lies between the
'reference temperature - hysteresis' and
the 'reference temperature', the device is
switched on and off with a PWM in steps
of 10% depending on the temperature
difference.
The lower the temperature difference, the
shorter the switch-on time. As a result of
the settability of the 100% value, the
PWM can be adapted to the heater size
and inertia. The signs are the opposite in
cooling mode.
In heating mode, the frost protection
function is always enabled. As soon as
the actual temperature drops below 8°C,
the temperature is controlled in the
selected operating mode to 8°C.
If one or several windows are open, the
output remains off provided the window/
door contacts FTK or Hoppe handles
are taught-in. In heating mode, however,
the frost protection remains enabled.
As long as all taught-in motion detectors
FBH detect no motion, the device is
switched to setback mode. In heating
mode, the reference temperature is set
back by 2°; in cooling mode, it is raised
by 2°. As soon as a motion detector
signals movement again, the device is
switched to normal mode.
When a wireless pushbutton is taught-in,
the assignment of the 4 keys is assigned
with the following fixed functions: Top
right: Normal mode (can also be enabled
by timer). Bottom right: Night setback
mode by 4°; in cooling mode, raised by
4° (can also be enabled by timer). Top
left: Setback mode by 2°, in cooling mode,
raised by 2°. Bottom left: Off (in heating
mode, frost protection enabled; in cooling
mode permanent off). If the motion
detector and wireless pushbutton are
taught-in at the same time, the last tele -
gram received is always the one that is
valid. A motion detector therefore switches
off a setback mode selected by wireless
pushbutton when a movement is detected.
Malfunction mode:
If a temperature sensor fails to receive a
wireless telegram for longer than 1 hour,
the LED lights up and the device switches
to fault mode. In heating mode, the device
remains switched on for 1.2 minutes at H1
and switched off for 2.8 minutes. When
set to H2 and H3 the 'ON' time is 4.5
minutes and 'OFF' time is 10.5 minutes.
The device is switched off in cooling
minutes
and
OFF
time
is 10
.
5
minutes
.
The device is switched off in cooling
mode. When a wireless telegram is
again received, the LED goes out and the
device switches back to normal mode.
The LED performs during the teach-in
process according to the operation
manual. It shows wireless control
commands by short flickering during
operation.
Typical connection
Technical data
Rated switching capacity 10A/250V AC
Standby loss (active power) 0.8W
Teaching-in wireless sensors in wire
-
less actuators
All sensors must be taught-in in
actuators so that they can detect and
executetheir commands.
Teaching-in actuator FHK
61U-230V
The teach-in memory is empty on
delivery from the factory. To ensure that
a device was not previously taught-in,
clear the memory completely:
Turn the upper rotary switch to CLR.
The LED flashes at a high rate. Within
10 seconds, turn the lower rotary switch
three times to right stop (turn clockwise)
and back again. The LED stops flashing
and goes out after 2 seconds. All taught-
in sensors are cleared; the repeater and
the confirmation telegrams are switched
off.

Chat with your Eltako FHK61U-230V manual using AI

Get instant AI answers from your Eltako FHK61U-230V manual

Ask anything about the Eltako FHK61U-230V. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend FHK61U-230V?

Yes No

Frequently Asked Questions

A

It is a wireless relay actuator for controlling heating or cooling equipment from compatible radio temperature controllers and sensors. It can switch loads up to 10 A at 250 V AC and supports room-based climate automation.

Is this answer helpful?

A

The actuator offers heating PWM modes with 4-minute and 15-minute cycles, heating two-point control, cooling PWM with a 15-minute cycle, and cooling two-point control. The selected mode should match the response behavior of the connected valves or equipment.

Is this answer helpful?

A

In heating operation, frost protection is always active. When the measured temperature drops below 8 C, the actuator regulates toward 8 C even if the output has otherwise been switched off or an open-window condition is present.

Is this answer helpful?

A

Yes. When compatible window or door contacts, or supported window handles, are learned into the actuator, the output remains off while one or more windows are open. Frost protection remains active in heating mode.

Is this answer helpful?

A

Yes. Units from production week 11/14 onward can learn encrypted sensors using a rolling-code method. Encrypted sensor setup requires a dedicated activation sequence and must be completed while power remains connected.

Is this answer helpful?

A

After more than one hour without a sensor telegram, the LED indicates fault mode. In heating modes, the actuator uses timed fallback switching. In cooling mode, it switches off. Normal operation resumes automatically when communication returns.

Is this answer helpful?

M: gpt-5.6-terra

Advantages and Disadvantages

Advantages

  • Combines heating and cooling control in one compact flush-mounted 230 V actuator.
  • Supports PWM and two-point control to suit thermal and motorized valve applications.
  • Works with temperature sensors, contacts, motion detectors, pushbuttons, and window handles.
  • Offers encrypted, bidirectional 868.3 MHz radio communication and optional repeater operation.
  • Provides frost protection, open-window shutdown logic, occupancy setback, and relay status feedback.
VS

Disadvantages

  • Installation requires a qualified electrician because the actuator operates from 230 V mains.
  • Only one temperature sensor can be learned at a time; adding another replaces the prior sensor.
  • Encrypted sensors may require re-learning after extended transmitter activity while the actuator is inactive.
  • Configuration relies on rotary switches and LED signals, which may be less convenient than app-based setup.
  • Cooling fault mode switches the output off when sensor telegrams are absent for over one hour.
M: gpt-5.6-terra

Product Specification

Type

Actuator

Standard

EnOcean, wireless bus (868 MHz)

Function

Switching actuator (on/off), temperature

Topology

Bus

Dimensions

1.77 x 1.77 x 1.3 in

M: gpt-5.6-terra

Product Description

Eltako FHK61U-230V Radio Actuator Heating-Cooling Relay, Switching Actuator - Read, Download & Print Free

The Eltako FHK61U-230V Radio Actuator Heating-Cooling Relay is a compact switching actuator designed to manage heating and cooling systems through wireless temperature control. Built for flush-mounted installation, it combines a potential-free relay contact with dependable radio communication, making it suitable for modern room-by-room climate control installations.

Operating from a 230 V supply, the unit provides a 10 A / 250 V AC switching capacity while consuming only 0.8 W in standby. Its compact 45 x 45 x 33 mm housing helps it fit into space-conscious electrical installations. The actuator retains its switching state during a power failure and returns to a defined off state when supply voltage is restored, supporting predictable system behavior after interruptions.

Flexible heating and cooling control

The FHK61U-230V evaluates signals from compatible wireless temperature controllers and sensors. It can also work with window and door contacts, motion detectors, wireless pushbuttons, and compatible window handles. This allows an installation to respond not only to room temperature but also to occupancy and open-window conditions.

For heating, the actuator offers frost protection that regulates toward 8 C when the measured temperature falls below this threshold. If paired window or door contacts report an open opening, the output is switched off while frost protection remains active in heating mode. Motion detectors can trigger setback operation when no movement is detected, reducing the target temperature by 2 C for heating or increasing it by 2 C for cooling.

Selectable control methods

Multiple operating modes let installers match control behavior to the connected system. Heating modes include pulse-width modulation with 4-minute or 15-minute cycles, plus two-point control. Cooling modes provide 15-minute pulse-width modulation and two-point control. Pulse-width modulation is particularly useful for matching output cycles to the response characteristics of thermal or motorized valve actuators.

An adjustable rotary setting provides a hysteresis range from 0.5 C to 4.5 C in 0.5 C steps. In PWM operation, this setting defines the temperature difference at which the output reaches 100 percent duty cycle. This creates a practical way to tune performance for radiator size, system inertia, and room comfort requirements.

Wireless integration and feedback

The actuator supports encrypted sensors, bidirectional radio communication, and an optional repeater function. Each change of the relay contact can be confirmed by a radio telegram. These confirmation signals can be learned by other compatible actuators or GFVS software, such as for synchronizing a circulation pump with heating valve activity.

A fault mode improves operational awareness when no temperature-sensor telegram is received for more than one hour. The LED indicates the condition, and heating modes use timed fallback switching while cooling switches off. Once sensor communication returns, normal operation resumes automatically.

Note: Installation on 230 V circuits must be performed by a qualified electrician. Allow the automatic synchronization process to finish before connecting switched loads to the mains.

M: gpt-5.6-terra

© Copyright 2026 Manual.ly