CyberPower PDU Manual
PDF manual · 39 Pages
English

Quick check
Incorrect answer, please try again.
Chat with your CyberPower PDU manual using AI
Get instant AI answers from your CyberPower PDU manual
Ask anything about the CyberPower PDU. Answers come from this manual, with the pages they are based on.
Ask a Question
Do you recommend PDU?
Yes NoFrequently Asked Questions
0HE (zero‑height enclosure) indicates a vertical, zero‑U PDU that mounts in the rack without consuming U space. Choose it to maximize usable rack units while providing high-density power distribution and retaining cable management within the cabinet.
Is this answer helpful?
Connect an Ethernet cable to the PDU’s network port. Use DHCP (default) or assign a static IP via CyberPower’s Power Device Network Utility, ARP command, or serial console. Access the web interface using the PDU’s IP and authenticate (default: cyber/cyber).
Is this answer helpful?
Obtain the two required firmware files from CyberPower, then upgrade via FTP, the Upgrade and Configuration Utility (recommended), or USB. Ensure FTP/utility settings are correct, do not power off the PDU during update, and verify firmware versions after reboot.
Is this answer helpful?
Daisy-chain connects up to four PDUs using the Out/In ports so one Host can monitor/control Guests under one IP. All PDUs must run compatible firmware; a maximum of four units is supported and some features (e.g., EnergyWise, WoL) may be Host-only.
Is this answer helpful?
Yes—switched models support per-outlet control, immediate or delayed on/off, reboot, and scheduling via the LCD or web interface, enabling planned reboots or shutdowns for maintenance or power management.
Is this answer helpful?
Optional ENVIROSENSOR connects via the PDU’s ENV/Daisy In port to provide temperature and humidity readings. Data is visible in the web UI and can trigger alerts or be included in logs and status reports.
Is this answer helpful?
Plug the PDU into a properly grounded three‑wire receptacle with the correct circuit protection (15A/20A/30A as applicable). Avoid adapters or extension cords, verify cord and plug condition, and never install during lightning storms or in wet/excessively hot environments.
Is this answer helpful?
Advantages and Disadvantages
Advantages
- High current support (up to 32A) in a space-saving 0U form factor suitable for dense racks.
- Networked monitoring and control via web, SNMPv1/v3, SSH/Telnet, USB and serial interfaces.
- Multifunction LCD displays voltage, current, frequency and network/firmware info for quick diagnostics.
- Daisy-chain capability allows monitoring up to four PDUs under one IP for simplified management.
- Flexible installation: reversible power cord, cord retention trays and multiple mounting options.
Disadvantages
- Default credentials (cyber/cyber) require immediate change to avoid security risks.
- Daisy-chain requires matching firmware versions and supports a maximum of four PDUs.
- Firmware upgrades require careful steps (two files) and network/USB access; improper updates risk issues.
- Zero‑U mounting can complicate cable management in some racks without dedicated vertical channels.
- Some features (EnergyWise, WoL) may be limited to Host PDU in daisy-chain setups.
Product Specification
Outputs
21x C13, 3x C19
Input
1x IEC 60309 (32A)
Input voltage
240V
Additional connections
1x RJ-45, 1x RS-232, 1x USB-A
Cable length
118.11in
Dimensions (WxHxD)
65.55x2.20x1.89in
Weight
17.64lbs
Features
rack-mountable, surge protection
Manufacturer's warranty
two years
Product Description
CyberPower PDU 0HE 32A — Reliable Rack Power Distribution
The CyberPower PDU 0HE 32A is a high-capacity, zero‑U power distribution unit engineered for dense rack environments and critical infrastructure. Designed to mount vertically inside server cabinets without occupying U space, this PDU supports up to 32A input and multiple outlet configurations to distribute power to servers, networking gear, and storage systems while preserving valuable rack real estate.
Built for data centers and edge installations, the 0HE 32A model integrates monitoring, control, and safety features. It includes a multifunction LCD that reports voltage, current, frequency, and firmware/network information; ethernet connectivity for remote management; and optional environmental sensor support for temperature and humidity monitoring. The PDU supports secure management via web interface, SNMP (v1/v3), Telnet and SSH, and can be configured through CyberPower utilities, serial console, DHCP or static addressing.
Practical installation features include multiple mounting options, cord retention trays, and reversible power cord orientation for tight cable channels. The unit provides circuit breakers for overload protection (depending on model), ground studs for proper grounding, and industry certifications (UL, CE, FCC) to meet safety and regulatory requirements. Firmware updates are supported via USB, FTP, or CyberPower’s Upgrade and Configuration Utility, enabling centralized maintenance and feature improvements.
Operationally, the PDU supports switched and metered models: switched units allow remote outlet control, reboot and scheduling; metered units provide per-bank or per-outlet power monitoring. The daisy-chain function enables up to four PDUs to be monitored from a single IP address (host/guest roles), simplifying management of multiple units while preserving the ability for each guest to remain network-accessible.
For shutdown coordination, CyberPower’s PowerPanel Business Edition integrates with the PDU to perform graceful unattended shutdowns of connected systems. LED indicators and an intuitive LCD provide immediate local status and alerts; logs and energy records can be consolidated on the host when daisy-chained. The product ships with mounting hardware, cable ties, and connectivity accessories depending on the exact SKU.
Whether you need high-current distribution for 3-phase or single-phase deployments or space-saving zero‑U mounting, the CyberPower PDU 0HE 32A balances robust electrical capacity with networked management and safety features to support modern rack infrastructure.
Notes
- Default management credentials: username "cyber", password "cyber" (change after initial setup).
- DHCP is enabled by default; fallback IP often documented in device label.
- Firmware upgrades require both firmware and data files; follow CyberPower utility or USB/FTP methods.
- Daisy-chain limits: up to 4 PDUs; firmware versions must match for full functionality.