BENNING CM E1
9
Operating Manual
BENNING CM E1
Earth measuring clamp for
- earth loop resistance measurement
- AC current/ leakage current measurement
Table of contents
1. User instructions
2. Safety instructions
3. Scope of delivery
4. Device description
5. General information
6. Ambient conditions
7. Electrical specifications
8. Measuring with the BENNING CM E1
9. Maintenance
10. Environmental note
1. User instructions
This operating manual is intended for
- skilled electricians and
- electrotechnically trained personnel.
The BENNING CM E1 is intended for measurements under dry ambient conditions. It must not be used
in electrical circuits with a nominal voltage higher then CAT III 300 V (see section 6 „Ambient conditions“
for details).
The following symbols are used in this operating manual and on the BENNING CM E1:
Application around and removal from HAZARDOUS LIVE conductors is permitted.
Warning of electrical danger!
Indicates instructions which must be followed to avoid danger to persons.
Attention! Must comply with documentation!
This symbol indicates that the information provided in the operating manual must be complied
with in order to avoid risks.
CAT III
CAT III Measuring category III is applicable to testing and measuring circuits connected to the
distribution circuit of the low-voltage mains installation of a building.
This symbol on the BENNING CM E1 indicates that the BENNING CM E1 is equipped with pro-
tective insulation (protection class II).
Please observe the operating manual!
This symbol appears on the display to indicate a discharged battery.
(AC) Alternating voltage or current
Ground (voltage against ground)

Chat with your Benning CM E1 manual using AI

Get instant AI answers from your Benning CM E1 manual

Ask anything about the Benning CM E1. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend CM E1?

Yes No
0
User Pic

Tina Boyle

3 months ago

Does the device calibrate itself, and are accessories included to check the calibration?

0
User Pic

Manual.ly

3 months ago

Yes. The device has a self-calibration function, and suitable resistance loops are included so you can verify the calibration when needed.

M: gpt-5.6-terra
M: gpt-5.6-terra

Frequently Asked Questions

A

The Benning CM E1 measures earth loop resistance, AC current, and AC leakage current. It is intended for checking earthing conductors and earth connections in suitable electrical installations.

Is this answer helpful?

A

Yes. It displays AC current and leakage current as True RMS values. The stated accuracy is based on sinusoidal waveforms, so accuracy can decrease when the waveform differs significantly from a sine wave.

Is this answer helpful?

A

Yes. The clamp method allows earth loop resistance testing around an earthing conductor or connection without disconnecting it or installing additional probes. It is especially suited to systems with multiple parallel earth connections.

Is this answer helpful?

A

The internal memory can store up to 116 measured values. Logging can be started manually or at selectable intervals between 1 and 255 seconds. A 0-second setting supports manual storage of individual readings.

Is this answer helpful?

A

The NOISE indicator signals detected interference that may affect a measurement. The jaw warning indicates that the clamp may not be closed correctly. Clean contact surfaces and fully close the jaws before testing.

Is this answer helpful?

A

The meter is designed for dry environments at 0 C to 50 C, up to 2000 m altitude, and CAT III 300 V circuits. Its IP30 rating provides no protection against water, so it should not be used in wet conditions.

Is this answer helpful?

M: gpt-5.6-terra

Advantages and Disadvantages

Advantages

  • Measures earth loop resistance without disconnecting the earth connection or placing auxiliary probes.
  • True RMS AC and leakage current measurement covers 0.300 mA to 35 A.
  • Internal logger stores up to 116 readings with manual or timed sampling from 1 to 255 seconds.
  • Adjustable HI and LO resistance alarms, HOLD mode, auto-ranging, and jaw-closure warnings support efficient testing.
VS

Disadvantages

  • Rated only for dry environments and IP30 protection, with no water protection.
  • CAT III rating is limited to 300 V, restricting use in higher-voltage applications.
  • Earth loop results can be affected by parallel grounding paths, interference, and jaw contamination.
  • Accuracy decreases at higher resistance ranges and with non-sinusoidal current waveforms.
M: gpt-5.6-terra

Product Specification

Measurement range

max. 1.5 kOhm

M: gpt-5.6-terra

Product Description

Benning CM E1 True RMS Clamp Meter Multimeter - Read, Download & Print Free

The Benning CM E1 True RMS Clamp Meter Multimeter is a specialist electrical testing tool designed for electricians and trained technicians who need dependable earth loop resistance and leakage current readings. Its clamp-based approach makes it possible to test grounding connections without disconnecting the earth conductor or installing auxiliary test probes. This helps streamline routine inspections in appropriate parallel grounding systems.

Built for Grounding and Leakage Current Checks

The meter measures earth loop resistance from 0.025 ohms to 1500 ohms, supporting checks on installations such as lightning protection networks, overhead line systems, pole grounding, and street lighting circuits. Because the displayed loop resistance includes the wider grounding path, results should be interpreted by qualified personnel with an understanding of the installation being tested.

It also measures AC and leakage current with True RMS performance. The available current ranges cover low leakage values from 0.300 mA through to AC current readings up to 35 A. True RMS measurement is useful when assessing alternating-current signals, although the stated accuracy is calibrated for sinusoidal waveforms.

Practical Controls and Memory Functions

A clear four-digit LCD provides measured values, status icons, battery indication, and warnings. The HOLD function freezes a reading for easier recording, while the internal logger can store up to 116 measurements. Users can select automatic sampling intervals from 1 to 255 seconds or save individual readings manually.

Configurable high and low resistance alarms add another layer of convenience during repeated checks. In alarm mode, the meter compares the measured earth loop resistance with preset limits and provides an audible warning when results fall outside the selected range. The acoustic alarm is disabled while data logging is active.

Design, Safety, and Everyday Handling

The Benning CM E1 has a maximum jaw opening of 38 mm and weighs approximately 750 g including its 9 V battery. It is rated for dry environments, CAT III 300 V applications, and operation from 0 C to 50 C. Automatic power-off normally activates after roughly four to six minutes, with an option to disable it when needed.

The clamp includes useful status indications for interference and incorrect jaw closure. A NOISE warning can appear when interfering signals are detected, while a separate icon alerts the user if the jaws are not closed correctly. Keeping the internal jaw contact surfaces clean is essential for reliable self-calibration and measurement performance.

Note: This instrument is intended for skilled electricians and electrotechnically trained personnel. Inspect it before use, observe voltage limits, work only in dry conditions, and arrange regular calibration to maintain specified accuracy.