X3-ULT-15K Maintenance Schedule
Inspect for physical damage and listen for any abnormal sounds during operation.
Inspect fans for dirt or abnormal sound. Clean with a soft dry cloth or brush, or replace if necessary.
Ensure all cables are firmly connected, check integrity for scratches, and verify sealing caps on idle terminals.
Check ground terminal and cable security. Use a Ground Resistance Tester to test resistance from enclosure to PE bar.
Check whether the heat sink is covered with foreign objects.
Free maintenance reminders
Timed to your purchase date. Always free, unsubscribe anytime.
Ask a Question
Do you recommend X3-ULT-15K?
Yes NoFrequently Asked Questions
The SolaX X3-ULT-15K is rated for 15 kW AC output and is part of the X3-ULTRA energy storage inverter series designed for grid-connected PV plus battery systems.
Is this answer helpful?
Yes. The inverter supports EPS mode for off-grid backup to supply critical loads. Configure EPS wiring and ensure EPS load does not exceed inverter peak output; follow start-up power guidance for inductive loads.
Is this answer helpful?
Use the Export Control function together with a CT or authorized meter to set the maximum export power. For parallel systems, configure the export limit on the master inverter and ensure proper meter/CT wiring.
Is this answer helpful?
The X3-ULT-15K is designed to work with SolaX lithium-ion battery systems. It has two BAT terminals (each up to 30 A). Follow SolaX battery documentation for string length, series/parallel schemes, BMS wiring and any required DC breakers.
Is this answer helpful?
COM1 and COM2 ports support BMS, parallel, RS485, DRM, meter/CT, ripple control and DIO connections. A WiFi/LAN dongle enables SolaX Cloud monitoring, and the inverter supports local LCD menus and app/web configuration.
Is this answer helpful?
Yes. The inverter supports parallel operation with a master/slave architecture. Maximum parallel counts depend on model and whether an X3-Parallel EPS Box is used; COM1 parallel wiring must adhere to distance limits.
Is this answer helpful?
Only qualified personnel should install the inverter. Ensure proper grounding, isolate AC and DC before service, respect PV voltage limits (max 1000 V), secure mechanical mounting, and use recommended breakers and insulated tools.
Is this answer helpful?
Advantages and Disadvantages
Advantages
- Flexible working modes (Self-use, Feed-in, Backup, Peak Shaving, TOU, EPS) for tariff and reliability optimization.
- Multi-channel MPPT and wide MPPT voltage range maximize PV harvest under mixed string conditions.
- Dual independent battery terminals allow scalable storage and support for SolaX lithium-ion packs.
- Comprehensive communications (BMS, RS485, DRM, meter/CT) and SolaX Cloud for monitoring and grid compliance.
- EPS output for whole- or partial-home backup and configurable export control for grid limits.
Disadvantages
- Requires qualified installers and careful configuration; complexity may be high for DIY users.
- Weighty (≈62 kg) and needs sturdy mounting and clearance for heat dissipation.
- Some functions (export control, parallel master settings, DRM) require additional accessories or master inverter setup.
- Battery compatibility limited to supported SolaX models; mixed battery expansion is not supported.
- Commissioning and meter/CT setup can be mandatory; improper wiring may trigger faults or void warranty.
Product Specification
Note
Prices partly include 0% VAT tax rates for AT and DE
Type
Hybrid inverter, without transformer, with fan, off-grid capable
Input voltage
130-1000V DC voltage (DC)
Max. input current
36A
MPP voltage range
160-950V DC voltage (DC)
Number of MPP trackers
2
Max. PV generator power
30kWp
Output power
15kW
Output phases
3-phase
Efficiency
98.0% max., 97.7% ηEU
Input
MC4
Output
Terminals
Interfaces
RJ-45, RS-485, Modbus RTU
Protection class
IP65
Ambient temperature
-40°F to +158°F
Dimensions
27.41x20.71x9.45in (WxHxD)
Weight
103.62lb
Product Description
SolaX Power X3-ULT-15K — Smart 15 kW Energy Storage Inverter
The SolaX Power X3-ULT-15K is a robust energy storage inverter in the X3-ULTRA family designed for residential and small commercial solar-plus-storage systems. With a rated output of 15 kW, it supports multi-channel MPPT, dual battery terminals, EPS backup, and a broad suite of smart modes that let you prioritize self-consumption, feed-in, backup readiness, peak shaving, TOU scheduling, or manual control. The inverter accepts PV inputs within a wide MPPT range, works with SolaX lithium-ion batteries and integrates with meters, CTs, EV chargers, data hubs and optional adapter boxes for flexible system designs.
Key features and operation
The X3-ULT-15K combines DC-to-AC conversion, multiple MPPT trackers and integrated surge protection to maximize PV harvest and safely supply the grid and local loads. It includes a clear LCD, local and cloud monitoring via a WiFi/LAN dongle, numerous communication ports (COM1/COM2) for BMS, RS485, DRM and meter/CT connections, and supports parallel operation with a master/slave topology. The inverter offers an EPS output for critical loads during outages and provides configurable export-control limits to meet local grid rules.
The unit offers several working modes to suit different priorities: Self-Use (loads > battery > grid), Feed-In Priority (loads > grid > battery), Backup (reserve SOC for outages), Peak Shaving (limit grid peaks), TOU (time-slot programmable modes), EPS (off-grid emergency supply) and Manual for commissioning or service. Forced charge and allowed discharge periods are configurable to shape battery behavior for tariffs or backup readiness.
Installation and safety highlights
Engineered for indoor or outdoor installation (IP66), the inverter demands qualified installation following local regulations. Important details include proper grounding, AC and DC isolation before servicing, adherence to PV string voltage limits (max 1000 V), correct battery wiring and the use of recommended breakers for grid and EPS connections. The manual stresses trained personnel for commissioning, clearances for heat dissipation, and safe handling due to weight and hot surfaces.
Monitoring and maintenance
Local LCD menus provide system status, history, and advanced settings; the SolaX Cloud and app enable remote monitoring and TOU schedule configuration. COM ports support parallel communication, BMS integration and metering; COM2 handles CTs, ripple control and DIO. Routine checks, firmware updates, fan replacement and troubleshooting procedures are detailed to ensure reliable long-term operation.
Notes:
- Compatible with SolaX battery systems; battery configurations and limits must be observed.
- Export control requires correct CT/meter installation and configuration on the master inverter in parallel setups.