fb4be96391eabbcc7a3e44f02d59998a5563 page 1
D6725-561-01 07/12
sKNX DALI gateway REG-K/1/16(64)/64/IP1MTN6725-0001© Merten 2009D6725-561-0107/12
¼
DANGER
Risk of fatal injury from electric shock.
All work on the device must only be carried out by
trained and skilled electricians. Note:
• The country-specific regulations
• The valid KNX guidelines
• The valid guidelines of the DALI standard
• The regulations for emergency lighting sys-
tems
The KNX DALI gateway REG-K/1/16(64)/64/IP1 (re-
ferred to below as the gateway) connects the KNX bus
with the DALI bus. Lights with DALI ECGs (electronic bal-
lasts) can therefore be integrated into an overall KNX ar-
chitecture and operated via the multitude of existing KNX
devices.
The device transforms switch and dim commands from
the connected KNX system into DALI telegrams and sta-
tus information from the DALI bus into KNX telegrams.
ECGs can be switched, dimmed and set to a defined val-
ue in 16 groups per gateway. In addition to group control,
the gateway offers the possibility to individually control
up to 64 ECGs.
|
Note
• The gateway is a Category-1 control unit. This
means the device must only be used in DALI
lines with connected ECGs and not with other
DALI control units within the line (no multi-mas-
ter function).
• Power supply for the up to 64 connected ECGs
comes directly from the gateway. An additional
DALI power supply is not required and not per-
mitted.
• Note that once ECGs have been assigned to a
group, they can no longer be controlled individ-
ually. An ECG can only be allocated to one
DALI group. The gateway does not support
multi-group allocations. If multi-group alloca-
tion is required, it must be performed via KNX
communication objects
KNX DALI gateway REG-K/1/16(64)/64/
IP1
Operating instructions
Art. no. MTN6725-0001
For your safety
Getting to know the Gateway
en
Numerous communication objects are available for the
visualisation of status and error information on an ECG
as well as group and gate-way level (current application:
11 communication objects per ECG and 8 communica-
tion objects per group, numerous individual objects).
In addition to all standard operating devices, the gateway
also allows the control of individual battery emergency
lights (EN 62386-202). For individual battery emergency
lights, a distinction is made between devices with switch-
able ECGs (usually emergency lights with one ECG) and
devices with non-switchable ECGs (converters), which
are usually used in connection with another “normal”
ECG (2 ECGs per light). The gateway allows for the
mixed control of different ECG types within a DALI line.
Emergency lighting systems with a central battery are
also supported.
A scene module for the extensive programming of up to
16 scenes from groups and individual ECGs as well as
an effect module for the control of processes and light ef-
fects are also available on the device.
The gateway enables different forms of DALI commis-
sioning (allocation of DALI ECGs to individual groups
and changes in configuration):
1. Commissioning on the device
2. Commissioning via integrated web server
The ETS with the data base entry of the current applica-
tion program is also required for the final commissioning
of the KNX communication.
Functions of the web server
The web server is accessed via the LAN network using a
PC, PDA or web panel. The internal websites can be
used to start up the device, and to configure, operate and
display all important functions.
|
For more details regarding the commissioning of
a DALI line, please see the current application de-
scription.
It is installed on a DIN-rail TH 35 according to EN 60715,
with the bus connection made via a bus connecting ter-
minal.
Mains connection and DALI lines are connected using
screw terminals on the device.
The device connectors as well as the programming but-
ton and programming LED that are required for commis-
sioning are only accessible in the distribution box when
the cover is removed.
The buttons (Move, Prg/Set, ESC) that are required to
commission and configure the DALI and the 2-line dis-
play and control LEDs (ERR und LNK) are accessible
when the cover is closed.
A RJ-45 plug for Ethernet connection
B KNX bus connection terminal
C Power supply connector
D DALI output connector
E Programming LED, normal/addressing mode
F Programming button, normal/addressing mode
G Move button, commission the device and set pa-
rameters
H Prg/Set button, commission the device and set pa-
rameters
I ESC button, commission the device and set param-
eters
J ERR-LED, signals fault status
K LNK-LED, signals Ethernet operational readiness
L Display 2x12 characters for DALI configuration
½
CAUTION
The device can become damaged!
The DALI output (D+, D-) does not have surge
protection. Connection AC 220/230 V will destroy
the device.
1 Set the gateway onto the DIN rail.
2 Attach the cable for DALI bus to the upper left termi-
nal.
Connections, displays and operating
elements
Mounting the Gateway
CB
E
D
I
G
H
J
K
L
F
A
A
B
C
2
1
3
D6725_561_01_EN.fm Seite 1 Mittwoch, 18. Juli 2012 8:29 08

Chat with your Schneider Electric REG-K/1/16(64)/64/IP1 manual using AI

Get instant AI answers from your Schneider Electric REG-K/1/16(64)/64/IP1 manual

Ask anything about the Schneider Electric REG-K/1/16(64)/64/IP1. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend REG-K/1/16(64)/64/IP1?

Yes No

Frequently Asked Questions

A

The gateway can connect and control up to 64 electronic ballasts (ECGs). These can be managed either individually or grouped into 16 separate groups.

Is this answer helpful?

A

Yes, the gateway supports individual battery emergency lights and central battery systems. It handles both switchable and non-switchable ECGs found in emergency fixtures.

Is this answer helpful?

A

It operates on AC/DC 100-240 V supply voltage and consumes a maximum of 7 W. It can also draw DC 24 V SELV power from the KNX bus, requiring approximately 5 mA.

Is this answer helpful?

A

No, the gateway provides power directly to the up to 64 connected ECGs. Adding an external DALI power supply is neither required nor permitted for this setup.

Is this answer helpful?

A

Commissioning can be done directly on the device using its buttons and display or remotely via the integrated web server accessed through a PC or PDA on the LAN network.

Is this answer helpful?

A

Once an ECG is allocated to a specific group, it cannot be controlled individually anymore. Each ECG can only belong to one DALI group unless multi-group allocation is handled via KNX communication objects.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Supports up to 64 individually controlled ECGs
  • Allows configuration of 16 lighting groups
  • Includes integrated web server for easy commissioning
  • Compatible with mixed ECG types and emergency lighting
  • Provides scene and effect programming modules
VS

Disadvantages

  • Cannot allocate ECGs to multiple groups simultaneously
  • DALI output lacks surge protection against AC connection
  • Requires strict adherence to safety insulation protocols
  • Limited to Category-1 control unit applications only
  • Physical access needed to distribution box for button operations
M: QW-35-FL

Product Specification

Type

Hardware Control Unit

Standard

KNX, LAN

Function

On/Off, Dimming Function, Gateway (KNX, DALI)

Topology

Bus

Features

IP20, Display

M: QW-35-FL

Product Description

Advanced Lighting Control with Schneider Electric KNX DALI Gateway

The Schneider Electric KNX DALI Gateway REG-K/1/16(64)/64/IP1 serves as a critical bridge between KNX bus systems and DALI lighting networks. This robust device allows electronic ballasts (ECGs) to be fully integrated into a comprehensive KNX architecture, enabling seamless operation through existing KNX devices. By transforming switch and dim commands from the KNX system into DALI telegrams, it ensures precise control over lighting environments.

This gateway supports flexible configuration by allowing lights to be switched, dimmed, or set to specific values across 16 distinct groups. Additionally, it offers the capability for individual control of up to 64 ECGs within a single line. The device acts as a Category-1 control unit, meaning it manages power supply directly to connected ECGs without requiring external DALI power sources. It also facilitates mixed control of various ECG types, including those found in battery emergency lighting systems compliant with EN 62386-202.

For advanced programming, the gateway includes scene modules capable of storing up to 16 scenes composed of group and individual ECG settings. An effect module further enhances functionality by controlling dynamic light processes and effects. Commissioning can be performed directly on the device using its built-in buttons and display or remotely via an integrated web server accessible through a LAN network. The internal websites allow users to start up, configure, and monitor all essential functions easily.

Installation is straightforward with DIN-rail mounting according to EN 60715 standards. The device features clear visual indicators such as LED status lights for errors and Ethernet readiness, along with a 2x12 character LC display for menu navigation. All connections, including mains, DALI, KNX, and Ethernet, are secured via screw terminals or standard RJ-45 plugs. Safety is prioritized with double basic insulation requirements between the KNX installation and power supply to prevent electrical hazards.

Key Features

  • Supports up to 64 individually addressable ECGs
  • Enables 16 configurable lighting groups
  • Includes integrated web server for remote management
  • Compatible with emergency lighting systems
  • Offers scene and effect programming capabilities

Important Notes

Ensure that the DALI output lines do not exceed 300 meters in length. Always use trained electricians for installation to avoid fatal injury risks from electric shock. The device does not support multi-master functions on the DALI line.