Manual.ly Logo

Schneider Electric Acti9 iCV40N VigiARC Manual

0.0 · 0 Ratings

PDF manual · 8 Pages

English

M: OA-GPT-5-NAN
page

/ 8

Loading...
c2a8d361b915110b62f8eb75faaf8e3a640d page 1
05/2021 1/8
MFR93179-00
Acti9 - iCV40N VigiARC - A9TDp36pp
PLEASE NOTE
b The installation, maintenance and eventual replacement of this device must only be
carried out by a qualied electrician.
b This device must not be repaired.
b All applicable local, regional and national regulations must be complied with during
the installation, use, maintenance and replacement of this device.
b This device should not be installed if, when unpacking it, you observe that it is
damaged.
b Schneider Electric cannot be held responsible in the event of non-compliance with
the instructions in this document and in the documents to which it refers.
b The service instruction must be observed throughout the life time of this device.
REMARQUE IMPORTANTE
b L’installation, l’entretien et le remplacement éventuel de cet appareil doivent être
e󰀨ectués uniquement par un personnel qualié.
b Cet appareil ne doit pas être réparé.
b Toutes les réglementations locales, régionales et nationales applicables doivent
être respectées lors de l’installation, l’utilisation, l’entretien et le remplacement de cet
appareil.
b Cet appareil ne doit pas être installé si, lors du déballage, vous observez qu’il est
endommagé.
b Schneider Electric ne peut être tenu responsable en cas de non-respect des
instructions contenues dans ce document et dans les documents auxquels il se réfère.
b Les instructions de service doivent être respectées tout au long de la durée de vie
de cet appareil.
TENGA EN CUENTA
b La instalación, el mantenimiento y el eventual reemplazo del equipo eléctrico solo
se debe realizar por personal cualicado.
b El equipo no debe repararse.
b Durante la instalación y el uso de este dispositivo, se deben cumplir todas las
normativas locales, regionales y nacionales aplicables.
b Este dispositivo no debe instalarse si, al desembalarlo, se observa que está
dañado.
b Schneider Electric no se hace responsable en caso de incumplimiento de las
instrucciones de este documento y de los documentos a los que se reere.
b Las instrucciones de uso se deben respetar durante toda la vida útil del producto.
NOTA
b Le operazioni di installazione, utilizzo, riparazione e manutenzione del presente
dispositivo elettrico devono essere eseguite esclusivamente da personale qualicato.
b Il dispositivo non deve essere riparato.
b Durante l’installazione e l’uso del presente dispositivo, è obbligatorio rispettare tutte
le normative locali, regionali e nazionali applicabili.
b Non installare il dispositivo se durante le operazioni di disimballaggio si nota che è
danneggiato.
b Schneider Electric non si assume alcuna responsabilità in caso di mancata
osservanza delle istruzioni riportate nel presente documento e nei documenti a cui
viene fatto riferimento.
b necessario rispettare le istruzioni di servizio per tutta la durata di vita del prodotto.
BITTE BEACHTEN
b Das elektrische Gerät darf ausschließlich von einem qualizierten Elektriker
installiert, verwendet, repariert und gewartet werden.
b Dieses Gerät darf nicht repariert werden.
b Bei der Installation und Verwendung dieses Geräts müssen sämtliche lokalen,
regionalen und nationalen Vorschriften eingehalten werden.
b Dieses Gerät darf nicht installiert werden, wenn Sie beim Auspacken
Beschädigungen feststellen.
b Schneider Electric kann keinesfalls für die Nichtbeachtung der Anweisungen in
dieser Anleitung oder Anweisungen in Dokumenten, auf die sie Bezug nimmt, haftbar
gemacht werden.
b Während der gesamten Produktlebensdauer müssen die Wartungsanweisungen
befolgt werden.
en fr es it de
en
Arc fault detection RCBO.
fr
RCBO Détecteur d’arc.
es
Interruptor automático diferencial con detector de arco eléctrico.
it
Interruttore magnetotermico di󰀨erenziale con protezione da arco.
de
Fehlerlichtbogen-Schutzeinrichtung mit FI/LS-Schutz.

Chat with your Schneider Electric Acti9 iCV40N VigiARC manual using AI

Get instant AI answers from your Schneider Electric Acti9 iCV40N VigiARC manual

Ask anything about the Schneider Electric Acti9 iCV40N VigiARC. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend Acti9 iCV40N VigiARC?

Yes No

Frequently Asked Questions

A

It combines arc-fault detection (AFDD), residual current protection (FI) with 30 mA Type A-SI sensitivity, and short-circuit/overload (LS) protection with a B-characteristic 13A trip setting and 6000 A breaking capacity.

Is this answer helpful?

A

No. Installation, maintenance, and replacement must be performed by a qualified electrician and comply with local, regional, and national regulations to ensure safety and correct operation.

Is this answer helpful?

A

Use the multifunction Test (T) button to run a self-diagnostic after installation and at regular intervals. Follow manufacturer instructions for periodic checks and use a suitable voltage tester to ensure circuits are de-energized before maintenance.

Is this answer helpful?

A

VISI-TRIP provides visual fault diagnosis for earth leakage, arc faults, and overvoltage events. Combined LEDs show specific fault types (parallel arc, series arc, earth leakage, overload/short-circuit, overvoltage, internal fault).

Is this answer helpful?

A

No. The device is not intended to be repaired. If it shows internal faults or is damaged, it should be replaced to maintain safety and compliance.

Is this answer helpful?

A

Yes. Disconnect all input and output conductors from the device before performing insulation resistance (dielectric) tests to avoid equipment damage.

Is this answer helpful?

A

Ideal for residential and light-commercial circuits—kitchens, living areas, bedrooms, and fixed-appliance feeds—where arc-fault detection and residual current protection significantly reduce fire and shock risks.

Is this answer helpful?

M: OA-GPT-5-NAN

Advantages and Disadvantages

Advantages

  • Integrated AFDD, residual current and overcurrent protection in a single compact 1P+N unit.
  • 30 mA Type A-SI improves detection of pulsating/DC leakage, enhancing shock and fire protection.
  • VISI-TRIP LED diagnostics and Test/Reset button simplify fault identification and routine checks.
  • 6000 A breaking capacity suitable for standard residential and light-commercial circuits.
  • DIN-rail mounting and top/bottom feed flexibility ease installation and retrofitting.
VS

Disadvantages

  • Must be installed and serviced only by qualified electricians, limiting DIY use.
  • Device is non-repairable — faults require replacement, increasing lifecycle cost.
  • Single-pole-plus-neutral may not suit three-phase or high-current industrial circuits.
  • Dielectric testing requires full disconnection of input/output cables, adding test prep time.
  • B-characteristic 13A rating may not match all circuit protection needs without coordination.
M: OA-GPT-5-NAN

Product Specification

Type

RCBO

Number of poles

1 + N

Rated voltage

230V

Rated current

13A

Rated residual current

30mA

Short-circuit breaking capacity

6kA

Residual current type

A-SI

Tripping characteristic

B

Degree of protection

IP20

Width

1.42 in

Module units

2

Special features

Arc fault detection device, neutral conductor on left

M: OA-GPT-54-NAN

Product Description

Schneider Electric Acti9 iCV40N VigiARC — Advanced AFDD + FI/LS Protection

The Schneider Electric Acti9 iCV40N VigiARC is a compact, single-pole-plus-neutral (1P+N) protective device that combines arc-fault detection (AFDD) with residual current and overcurrent protection (FI/LS). Rated 13A with a B-characteristic tripping curve, 30 mA residual sensitivity (Type A-SI) and 6000 A fault breaking capacity, this device is designed for modern residential and light-commercial electrical installations where fire risk reduction and personnel safety are priorities.

Key product highlights

This Acti9 unit integrates multiple protection functions in one DIN-rail mountable module: parallel and series arc detection, earth leakage detection, short-circuit and overload protection, and clear diagnostic indication. A multifunction Test/Reset button enables periodic self-checks and on-demand diagnostics, while a VISI-TRIP indicator and LEDs provide immediate, readable fault cause information. The device supports top or bottom feeding and includes clear installation cues for qualified electricians.

Why it matters

Arc faults are a common cause of electrical fires; combining AFDD with residual current protection and overcurrent tripping reduces both ignition sources and electric shock risk. The 30 mA Type A-SI sensitivity improves detection of pulsed and smooth DC components in leakage currents, while the 6000 A breaking capacity suits typical distribution circuits. The compact 1P+N format conserves panel space and simplifies retrofits.

Typical applications

  • Family homes and apartments where wiring aging or damaged cords pose fire risk
  • Small commercial units and tenant-fit outs requiring enhanced protection without large switchgear changes
  • Circuits feeding fixed appliances, kitchens, bedrooms, and living areas where arc detection adds safety

Practical use and maintenance

Installation and wiring must be performed by qualified electricians following local regulations. After installation, run the device’s self-diagnostic test using the T button and repeat periodically. Follow the device’s dielectric test guidance and always isolate inputs/outputs before high-voltage testing. If packaging is damaged or internal faults appear (product out of order), replace rather than repair.

Notes

  • Device must not be repaired; follow service instructions for lifetime compliance.
  • Disconnect all conductors before dielectric tests to avoid equipment damage.
  • Always de-energize circuits and verify with an appropriate voltage tester before maintenance.
M: OA-GPT-5-NAN

© Copyright 2026 Manual.ly