eb114a8c2123d2d2a72b0feacb545aa83c42 page 5
Valves, controls + systems
Thermostatic radiator valves
Thermostats “Uni LH” and “Uni LD”
Installation instructions
T
he Oventrop Quality Management System
is certified to DIN-EN-ISO 9001
Contents:
Page 5 General information
Valve installation
Thermostat installation
Figures and symbols on the thermostat
Page 6 Limiting the control range
Page 7 Blocking the temperature setting
Recalibration
Cancellation of limitation or blocking
Page 8 Replacement of the gland nut
Checklist for faults
General information
Thermostatic radiator valves control the room tempera-
ture by modifying the flow of hot water through the ra-
diator. Often, there is only a minimum requirement for
heat (especially in transition periods) and so the ther-
mostats only open the valves a small amount. Conse-
quently flow noises could occur due to high differential
pressures. To prevent these noises, measures should be
taken to influence the differential pressure; for example
by using adjustable circulation pumps, manually adjusta-
ble bypass pipes, differential pressure regulators or diffe-
rential pressure relief valves.
It is recommended to adjust the temperature of the sup-
ply pipe to the outside temperature, preferably by using
a weather guided temperature controller.
Fur further information see “User instructions” and
technical data sheets “Thermostats” and “Ther-
mostatic radiator valves”.
Valve installation
The radiator valve should be installed so that the ther-
mostat is in a horizontal position and a good circulation
of air is guaranteed. If this is not possible, a thermostat
with remote sensor or with remote control should be
used. It is most important that capillaries are not kinked
or flattened.
The radiator valve is installed in the supply pipe to the ra-
diator, with the flow in the direction of the arrow.
When using compression fitting, the thread of the fitting
and the compression ring are slightly oiled at works. Do
not use any additional lubricant! Do not allow the oil or
lubricant to come into contact with the EPDM valve disc.
EPDM is not oil resistant.
Only use Oventrop compression fittings.
It is important that the pipes are cut to the correct length
at a right angle to the centre line. The ends of the pipe
must be free of burrs and undamaged.
When using thin walled and very soft pipes, reinforcing
sleeves have to be used. The reinforcing sleeve supports
t
he pipe and provides the strength to enable the neces-
sary compression. Reinforcing sleeves cannot be used on
pipe with welded seams. The recommendations of the
pipe manufacturers have to be observed in any case. If
necessary, a practical “test” has to be carried out.
The special fittings “Cofit” may be used for the Oventrop
composition pipe “Copipe”. The installation instructions
supplied with the fittings must be observed.
All radiators and pipework must be flushed thoroughly to
prevent any problems caused by welding beads or dirt.
When converting old heating systems, it is recommended
that a plastic strainer should be fitted at the inlet port of
all radiator valves.
Do not fit the thermostat until all building work has been
completed. During construction period, the valve can be
operated with the screwed cap. The screwed cap is not
to be used for permanent shut-off of the valve against sy-
stem pressure (e.g. while radiator is removed). In this
case protect the valve outlet with a metal cap.
Thermostat installation
To ensure an easy installation, the handgrip must be ope-
ned to the maximum position (figure “5”). In this positi-
on, the collar nut (“Uni LH”) or the squeeze connection
(“Uni LD”) of the thermostat may be easily fitted to the
valve body.
Turn the thermostat so that the indicator mark is facing
up. Hold in this position and tighten collar nut without
using excessive force.
Figures and symbols on the thermostat
Compression fitting before
tightening. Remove pipe
insulation far enough.
Pipe shape after tightening.
Reinforcing ring
Compression nut
Compression
ring
Collar nut “Uni LH” or
squeeze connection ”Uni LD”
Tactile setting device
Indicator mark
Minor graduation
Direction “warmer”
Basic setting “3“, about 20 °C
Direction “colder”
Graduation figure
Tactile setting device
Handgrip
Memory disc
(0 = complete shut-off
This symbol is only to be found on
thermostats with a shut-off facility)
✽ = Frost protection symbol
in this position the valve opens automatically when
room temperature drops below 7 °C.
1 = about 12 °C
2 = about 16 °C
3 = about 20 °C
4 = about 24 °C
5 = about 28 °C
The minor graduations
between the figures 2 - 4 represent
a change of room temperature of
about. 1 °C.
}
EN
5

Chat with your Oventrop Uni LH manual using AI

Get instant AI answers from your Oventrop Uni LH manual

Ask anything about the Oventrop Uni LH. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend Uni LH?

Yes No

Frequently Asked Questions

A

It regulates room temperature by adjusting the flow of hot water through the radiator. This helps keep indoor temperatures stable and comfortable while improving heating efficiency.

Is this answer helpful?

A

The numbered scale corresponds to approximate room temperatures. For example, 1 is about 12 °C, 2 about 16 °C, 3 about 20 °C, 4 about 24 °C, and 5 about 28 °C. The frost symbol protects against freezing.

Is this answer helpful?

A

It should be mounted horizontally so room air can circulate freely around it. If that is not possible, a remote sensor or remote adjustment version should be used to keep temperature sensing accurate.

Is this answer helpful?

A

Yes. Clips inside the handgrip can limit the minimum and maximum setting. This is useful when you want to keep the thermostat within a safe or controlled range, such as in care facilities or common rooms.

Is this answer helpful?

A

Yes. Any desired temperature can be blocked by repositioning the internal clips. This prevents unauthorized changes and keeps the thermostat fixed at one set point.

Is this answer helpful?

A

The unit can be recalibrated. The manual explains how to remove the handgrip, realign the sensor casing, and reset the factory reference point, usually around 20 °C.

Is this answer helpful?

A

Leaks may come from a loose gland nut, a worn O-ring, or a loose valve insert. Noise often points to wrong flow direction, trapped air, pump imbalance, or high differential pressure. The system should be checked step by step.

Is this answer helpful?

M: OA-GPT-54-NAN

Advantages and Disadvantages

Advantages

  • Clear numbered settings with tactile guidance make temperature control simple and precise.
  • Limit and lock functions help prevent unwanted changes in shared or sensitive spaces.
  • Horizontal mounting and remote sensor options improve accuracy in difficult installations.
  • Some service tasks, such as gland nut replacement, can be done without draining the system.
VS

Disadvantages

  • Installation must be done carefully; poor pipe preparation or alignment can cause issues.
  • Capillary tubes are sensitive and must not be bent or flattened during mounting.
  • Noise problems may still occur if system pressure and pump settings are not balanced.
  • Several parts and procedures are model-specific, so incorrect replacements can be a problem.
M: OA-GPT-54-NAN

Product Specification

Type

Actuator

Function

Heating control, Thermostat, Temperature

Dimensions

2.56x3.94x5.12in

M: OA-GPT-54-NAN

Product Description

Oventrop Uni LH Radiator Thermostat: Smart Heating Control for Everyday Comfort

For anyone searching for the Oventrop Uni LH radiator thermostat Manual, the core message is simple: this thermostat is built to make radiator heating more precise, more comfortable, and easier to manage. The Uni LH and Uni LD models are designed to regulate room temperature by controlling how much hot water flows through the radiator, helping create a stable indoor climate without constant manual adjustment.

One of the strongest points of this product line is its practical installation logic. The thermostat should be mounted horizontally so room air can circulate freely around it, which improves accuracy. In more difficult installations, a remote sensor or remote control version can be used instead. The instructions also stress clean pipe preparation, correct flow direction, and careful handling of compression fittings to avoid damage and unwanted leaks.

The control head offers a familiar numbered scale from frost protection to higher comfort settings, with the factory default usually centered around 20 °C on setting 3. That makes everyday operation intuitive, but the thermostat goes further than basic temperature selection. It can be limited to a safe range or blocked at a fixed setting using clips inside the handgrip, which is especially useful in shared buildings, care homes, hallways, bedrooms, or rooms where tampering should be prevented.

Another advantage is serviceability. The thermostat can be recalibrated if the setting has drifted, and the gland nut can be replaced without draining the heating system on supported valve types. The manual also includes troubleshooting guidance for common issues such as poor heat output, flow noise, leaking valves, air in the system, blocked strainers, or reversed pipe connections. That makes the product feel less like a simple control and more like a complete heating management tool.

Notes

  • Keep the thermostat away from curtains, panels, and other obstructions.
  • Avoid oil or grease contact with EPDM parts.
  • Dispose of defective units as hazardous waste and return them to the manufacturer when possible.
  • If flow noise appears, check differential pressure, pump settings, and system balancing.

Overall, the Oventrop Uni LH radiator thermostat stands out as a dependable, professional-grade solution for precise room control. It combines straightforward comfort settings with installation discipline, protection against misuse, and maintenance-friendly details that make it a strong choice for modern heating systems.