The switch actuator, flush-mounted/230/16 is an
intelligent relay with bus capability. The device has a
switched relay output and enables the switching of
luminaires and other loads.
The function of the channel is determined by the
downloaded application software.
¼
Danger due to electrical current:
All work carried out on the unit may only be
performed by skilled electricians. The country-
specific regulations and the valid EIB guidelines
must be followed.
The switch actuator, flush-mounted/230/16 can be
used flexibly and installed in a wall or ceiling box (in
accordance with DIN 49073 Form B) with a diameter
of 60 mm due to its compact size. For ceiling
mounting, the ceiling hook on which the luminaire is
suspended can be screwed onto the ceiling box
through the centre hole in the switch actuator.
½
Attention:
If socket-outlets are switched with the switch
actuator, the circuit must be fused at 10 A as it
cannot be guaranteed that only pure ohmic
loads are connected. This fusing can be carried
out with the SCHUKO socket-outlet insert with
fine-wire fuse.
The device is housed in a plastic enclosure and is
supplied with an integrated bus coupler. The bus line
is connected via the bus connecting terminal. The
switched output and the mains voltage are connected
via two screw terminals.
½
Attention:
You must ensure that a safety clearance is
maintained in accordance with DIN VDE 0110
Part 1. A distance of at least 4 mm must be
maintained between individual cores of the 230
V cable and the bus cable.
Suggested installation:
– The opposite entry openings of the installation box
should be used for the 230 V low-voltage cables and
the bus cable.
– The sheath of the bus cable must be cut back as
short as possible at the bus terminal.
– The flush-mounted switch actuator itself serves as
a separating web.
Connection example:
After wiring the device, the assignment of the physical
address and the parameterisation are carried out:
1 Connect the interface to the bus
2 Connect the bus voltage to the system
3 Press the programming button in the device (red
programming LED lights up)
4 Download the physical address from the ETS via
the interface (red programming LED goes out)
5 Load the application with the corresponding
parameterisation into the device via the interface
6 Connect the mains voltage to the system
7 When the device is ready for operation, check the
required function (also possible using ETS)
Bei Warenrücksendungen auf Grund von
Beanstandungen wenden Sie sich bitte an unser
Service Center:
Merten GmbH & Co. KG, Lösungen für intelligente Ge-
bäude, Service Center, Fritz-Kotz-Straße 8,
Industriegebiet Bomig-West, D-51674 Wiehl
Telefon: +49 2261 702-204
Telefax: +49 2261 702-136
Internet: www.merten.de
Bei technischen Fragen wenden Sie sich bitte an
unsere InfoLine:
Telefon:+49 1805 212581* oder +49 800 63783640
Telefax:+49 1805 212582* oder +49 800 63783630
*kostenpflichtig / fee required
Switch actuator, flush-mounted/230/16
Colour
polar white
Article no.
629993
1. Function
2. Installation
AC 230V
µ 16A
address:
629993
Schaltaktor UP/230/16
Switch actuator FM/230/16
A Bus connecting terminal, max. 4 core pairs
B Connection of the 230 V low-voltage cable
C Programming LED (red LED)/programming button
A Bus coupler
A
B
AC 230V
µ 16A
address:
629993
Schaltaktor UP/230/16
Switch actuator FM/230/16
C
Bus
+ -
A
N
L
L1
3. Commissioning
4. Technical data
External auxiliary
voltage:
none
Power supply from the
bus: DC 24 V/approx. 10 mA
Insulation voltage: 4 kV between bus and
AC 230 V
Switch contacts: 1 x make contacts
Nominal voltage: AC 230 V, 50 to 60 Hz
Nominal current: 16 A at cos ϕ =1
10 A inductive load at
cos ϕ =0.6
Connected load:
Incandescent lamps: AC 230 V, max. 2700 W
with 20,000 switching
cycles
Halogen lamps: AC 230 V, max. 1700 W
with 20,000 switching
cycles
Fluorescent lamps: AC 230 V, max. 1000 VA,
with parallel correction,
with 5,000 switching
cycles
Capacitive load: AC 230 V, 10 A, max. 105 μF
with 5,000 switching
cycles
Fuse: The switch contact must be
protected by a series-
connected circuit-breaker
Switching frequency: max. 10 per minute at
nominal load
Ambient temperature:
Operation: -5 °C to +45 °C
Storage: -25 °C to +55 °C
Transport: -25 °C to +70 °C
Environment: can be used at up to 2000
m above sea level (MSL)
Operating elements: Programming button
Display elements: Red LED for checking the
bus voltage and for
entering the physical
address
Connections:
Bus: via two 1 mm pins for bus
connecting terminal
Outer conductor: two screw terminals for
max. 2.5 mm²
EC guidelines: corresponds to low-voltage
guideline 73/23/EEC;
corresponds to EMC
guideline 89/336/EEC
Dimensions: 51x52x29 mm (WxHxD)
V6299-582-00 03/06

Chat with your Merten KNX Switch Actuator UP/230/16 manual using AI

Get instant AI answers from your Merten KNX Switch Actuator UP/230/16 manual

Ask anything about the Merten KNX Switch Actuator UP/230/16. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend KNX Switch Actuator UP/230/16?

Yes No

Frequently Asked Questions

A

The device supports a nominal current of 16 amperes at cosine phi equals 1. For inductive loads at cosine phi 0.6, the limit is 10 amperes. Incandescent lamps can handle up to 2700 watts safely.

Is this answer helpful?

A

Mount it in a DIN 49073 Form B box with a 60 mm diameter. Use opposite entry openings for power and bus cables. Keep bus cable sheaths short near the terminal block.

Is this answer helpful?

A

Yes, but you must protect the circuit with a 10 ampere fuse because ohmic loads are not guaranteed. Use a SCHUKO socket outlet insert with a fine-wire fuse for safety.

Is this answer helpful?

A

You need the Electronic Training System or ETS software to download the physical address and load application parameters. Connect via the interface terminal to program the device.

Is this answer helpful?

A

Absolutely. All work must be done by skilled electricians due to dangerous electrical currents. You must follow local laws and valid EIB guidelines to ensure personal safety.

Is this answer helpful?

A

Operation is permitted between minus five degrees Celsius and plus forty-five degrees Celsius. Storage and transport allow wider ranges down to minus twenty-five degrees.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Compact design fits standard 60 mm installation boxes easily.
  • Integrated KNX bus coupler simplifies network connectivity.
  • Flexible load handling for lights and various consumers.
  • Robust plastic housing offers good durability and safety.
  • Easy programming with visible red LED indicator status.
VS

Disadvantages

  • Requires skilled electrician for safe voltage connection.
  • Socket circuits need additional 10 A fuse protection.
  • Strict safety clearance required between power and bus wires.
  • Limited to 16 A nominal current capacity per channel.
  • Bus cable sheath must be cut back very short carefully.
M: QW-35-FL

Product Specification

Type

Actuator

Standard

KNX

Function

Switch Actuator (on/off)

Dimensions

2.91x2.91x1.26in

Features

IP20

M: QW-35-FL

Product Description

Merten KNX Switch Actuator 1-Way Smart Home Solution

Experience superior automation with the Merten KNX Switch Actuator 1-way 230V 16A In-Wall Switch Actuator Manual. This intelligent device serves as the backbone for efficient building management systems. It allows users to control lighting and consumer loads remotely through a standardized KNX bus network. Designed for modern interiors, it ensures seamless integration and reliable performance.

Installation and Physical Build

The unit fits into standard wall or ceiling boxes measuring 60 mm diameter. Its compact dimensions of 51 by 52 by 29 millimeters save space inside junctions. The housing is made from durable plastic providing robust protection. Installation requires strict adherence to electrical safety guidelines. Technicians must verify clearances between the bus cable and mains voltage.

Electrical Performance Standards

Operating at AC 230 volts, this actuator supports up to 16 amperes of current. It handles various lamp types including incandescent and halogen bulbs efficiently. Inductive loads are capped at ten amperes for safety. Capacitive loads require parallel compensation to prevent damage. The device manages switching frequencies up to ten times per minute under normal load conditions.

Commissioning and Setup

Configuring the system involves seven simple steps outlined in the documentation. First connect the interface to the KNX bus infrastructure. Then power up the voltage supply and press the programming button. The red LED indicates active mode. Download the physical address from the ETS software to link the device. Finally test the functionality to confirm correct operation parameters.

Safety Protocols and Maintenance

Always follow country-specific regulations when working with electricity. Protect socket circuits with a ten ampere fuse for variable loads. Maintain a four millimeter distance between different wire cores during wiring. Store units between minus twenty-five degrees and plus fifty-five degrees Celsius. Service inquiries can be directed to the manufacturer's support center for warranty issues.

Important Notes

  • Work must be performed by qualified electricians.
  • Ensure compliance with EMV guidelines 89/336/EEC.
  • Use SCHUKO inserts for switched outlets.
  • Verify insulation voltage of four kilovolts.