General technical data
Instruction manual
BA TS3x10 GS3x10 GS4xx0 knx Hardware HM; de, en -24093- 2021.09V03
en
Disconnect device from power supply for wiring and
installation purposes! Check power supply is disconnected!
Step 1:
Step 2:
Step 3:
Step 4:
Attention! You have to check and consider the
safety instructions above!
Mounting
!
www.hugo-mueller.de
Manual adjustment
Set-point temperature
manually adjustable via
touch-area (depend on model)
Display with LEDs.
Default:
Adjustment range ±3 °C with
0.5 °C increment
Open the device with a small screw driver by pushing in the
lever at the bottom of the housing and gently remove the
front part.
Fix the rear part, either directly to the wall or on a
flush-mounting box.
After the wiring, press the “programming button” to set the
device into programming mode.
(this can be done at a later time as well)
Reattach the front part.
This device is suitable for wall mounting or for mounting on a
§
flush-mounting box.
Ensure that no dust gets inside the device.
§
After initial startup, the device requires up to 2 minutes until the sensor
§
sends the first values.
Supply voltage
Bus current
Bus system
Inputs
(except GS4x.00knx)
Permitted ambient
temperature
Housing
Housing color
Mounting
Type of connection
Type of protection
Class of protection
Type of connection
external inputs
via KNX bus voltage
< 10 mA
KNX
5 binary and analog inputs
I4 + I5: For external temperature sensor input
(PT1000 or müller TF06 (10kΩ))
0 ... 50 °C
self-extinguishing thermoplastic
studio white (similar to RAL 9016)
jet black (similar to RAL 9005)
specific colors on request
wall mounting
(preferrably combined with flush-mounting box)
push-in connector
IP 20 (DIN EN 60529)
III when installed according to regulations
wire diameter max. 6 x 0,5 mm²
strip length 7 mm
Product specific technical data
Sensors
Co2 (measuring range: 390...5.000 ppm (air pressure compensated))
relative humidity (measuring range: 0...100 %)
temperature (measuring range: 0...+50 °C)
atmospheric pressure (measuring range: 300...1.100 hPa)
dew point
VAV ventilation control
GS 3x.x0 knx
relative humidity (measuring range: 0...100 %)
temperature (measuring range: 0...+50 °C)
atmospheric pressure (measuring range: 300...1.100 hPa)
dew point
VAV ventilation control
TS 3x.x0 knx
temperature (measuring range: 0...+50 °C)
Temperature: ± 0,5 °C
Relative humidity: ± 3%
CO2: ± 30 ppm ± 3 %
Source of interference
The sensor values of the device can be negatively influenced by
external impacts as e.g.:
Draught and air movement: e.g. through windows, doors,
§
convection, heating and people
Warming and cooling:
§
e.g. sunlight or mounting on an outside wall
Heat sources: close to installed electrical consumers
§
e.g. dimmers
Vibrations or shocks, which the unites are or were subjected to
§
Pollution due to colors, wallpaper paste, dust
§
e.g. at renovation work
Organic solvents or their vapours: e.g. detergents
§
Plasticizers from stickers and packaging
§
e.g. bubble wrap or polystyrene
CO2 accuracy is valid under following conditions:
1 ) after 3 weeks of operation
2 ) initial base line calibration; manually or via ETS-object
3 ) once a week fresh air exposure
4 ) ventilation strategy:
first threshold CO2 should be ≤ 800 ppm
The tolerances are valid at a typical and stable ambient room
temperature.
When using a flush-mounting box, the use of air-tight boxes is
recommended.
Tolerances
Step 1:
Step 2:
Step 3:
Step 4:
!
Programming button:
Please press in this area directly
on the circuit board!
front part
front part
rear part
3°
+3°
-
GS 4x.x0 knx
Inputs 1-5, GND
KNX
!
CAUTION! DANGER OF FIRE AND ELECTRIC SHOCK!
!! Installation and assembly of electrical equipment must be carried out only by a skilled person !!
Connect only to suitable supply voltage [KNX bus voltage (nominal voltage 29V)].
§
§ Warranty void if housing opened by unauthorized person!
§ The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if external in
fluences exceed certain limits!
§ Installation and assembly of electrical equipment must be in accordance with national building, electrical and safety codes!
§ Defective devices / sensors have to be put out of service immediately!
§ Observe the regulations and instructions in the ZVEI/ZVEH handbook (building system technology). Especially the
professional installation of the bus lines and the professional installation and start-up of KNX devices must be observed!
The device can be used in following applications: monitoring of the air quality in building systems technology
§
(schools, offices, hotels, conference venue etc.), data transfer and regulation via bus system.
The device is intended for use in accordance with the defined technical data.
§
The device is not qualified for security relevant tasks such as emergency doors, fire protection equipment, fermenting
§
cellars etc.
The inappropriate use of the device can cause damage to property and persons.
§
The device is not intended for use of unauthorized constructional alterations, repairs and security relevant tasks
§
The device is not intended for use in outdoor areas and wet rooms
§
The device has to be disposed in an environmentally friendly manner according to the current electrical codes!
§
!
Safety instructions / Intended use and inappropriate use / Disposal
-
To disconnect the
wires, push in the
blanked out area of
the push-in connector!
-
1
2
3
4
5

Chat with your Hugo Muller GS 40.10 KNX manual using AI

Get instant AI answers from your Hugo Muller GS 40.10 KNX manual

Ask anything about the Hugo Muller GS 40.10 KNX. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend GS 40.10 KNX?

Yes No

Frequently Asked Questions

A

The device includes sensors for CO2 (390-5000 ppm), relative humidity (0-100%), temperature (0-50°C), atmospheric pressure (300-1100 hPa), and dew point calculation.

Is this answer helpful?

A

No. Installation must be performed exclusively by a qualified electrician to ensure safety and compliance with electrical codes. Unauthorized opening voids the warranty.

Is this answer helpful?

A

After initial startup, the device requires approximately two minutes to stabilize and provide the first sensor values to the KNX system.

Is this answer helpful?

A

No, the device is strictly designed for indoor use only. It is not rated for outdoor environments or wet rooms.

Is this answer helpful?

A

Accuracy can be affected by drafts, direct sunlight, nearby heat sources, vibrations, and improper calibration. A three-week warm-up is required for full precision.

Is this answer helpful?

A

Yes, the model-dependent touch interface allows for manual set-point temperature adjustments with a default range of ±3°C in 0.5°C increments.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Comprehensive multi-sensor capability including CO2, humidity, temperature, and pressure
  • Seamless integration with KNX bus systems for centralized building management
  • User-friendly manual temperature adjustment via intuitive touch interface
  • Durable construction with self-extinguishing thermoplastic housing
  • Supports advanced VAV ventilation control strategies for energy efficiency
VS

Disadvantages

  • Requires installation by a certified electrician due to high safety risks
  • Measurement accuracy can be compromised by drafts, heat sources, or vibrations
  • Not suitable for security-critical applications like fire doors or emergency exits
  • Cannot be used in outdoor areas or wet rooms under any circumstances
  • Initial calibration requires a three-week warm-up period for optimal performance
M: QW-35-FL

Product Specification

Type

Sensor, Actuator

Standard

KNX

Function

Air quality, Humidity, Temperature

Topology

Bus

Dimensions

3.17x3.17x0.67in

Features

IP20

M: QW-35-FL

Product Description

Hugo Muller GS 40.10 KNX Room Climate Controller and Air Quality Sensor

The Hugo Muller GS 40.10 KNX Room Climate Controller represents a significant advancement in building automation, specifically designed to optimize indoor environmental quality through precise monitoring and control. This sophisticated device integrates seamlessly into KNX bus systems, making it an ideal solution for schools, offices, hotels, and conference centers where air quality is paramount. By combining temperature, humidity, CO2, and atmospheric pressure sensing capabilities, the unit ensures that occupants enjoy a healthy and comfortable atmosphere at all times.

At the heart of this controller lies a robust sensor array capable of measuring CO2 levels within a range of 390 to 5,000 ppm, relative humidity from 0 to 100 percent, and temperatures between 0 and +50 degrees Celsius. The inclusion of atmospheric pressure and dew point data allows for comprehensive climate analysis, enabling automated ventilation strategies that respond dynamically to changing conditions. The device features a sleek housing available in studio white or jet black, fitting modern architectural aesthetics while maintaining durability through self-extinguishing thermoplastic materials.

Installation is straightforward for qualified electricians, supporting both wall mounting and flush-mounting box configurations. The unit utilizes push-in terminals for secure connections with wires up to 6 x 0.5 mm². Once powered via the KNX bus voltage, the system requires approximately two minutes to initialize and begin transmitting accurate sensor values. A manual adjustment feature allows users to fine-tune set-point temperatures directly via the touch interface, offering flexibility without compromising automated control logic.

It is crucial to note that the accuracy of CO2 measurements depends on specific operational conditions, including a three-week warm-up period and weekly fresh air exposure. Proper placement away from drafts, heat sources, and direct sunlight is essential to maintain measurement integrity. This controller is strictly intended for indoor use and should never be deployed in wet rooms or outdoor environments. Its intelligent design supports VAV ventilation control, ensuring energy efficiency while maintaining optimal air quality standards.