5. Storage and Maintenance
Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.
Symptom
Possible cause
Remedy
Fault code is shown as 14 on LCD
display and alarm is continuously
sounding.
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
Check output wiring and if
connected devices are in
short circuit status.
Fault code is shown as 01, 02, 03,
11, 12, 13 and 41 on LCD display
and alarm is continuously
sounding.
A UPS internal fault has
occurred. There are two
possible results:
1.
The load is still supplied,
but directly from AC power
via bypass.
2.
The load is no longer
supplied by power.
Contact your dealer
Battery backup time is shorter
than nominal value.
Batteries are not fully
charged
Charge the batteries for at
least 5 hours and then
check capacity. If the
problem still persists,
consult your dealer.
Batteries defect
Contact your dealer to
replace the battery.
Fault code is shown as 2A on LCD
display and alarm is continuously
sounding.
The short circuit occurs on
the charger output.
Check if battery wiring of
connected external pack is
in short circuit status.
Fault code is shown as 45 on LCD
display. At the same time, alarm is
continuously sounding.
The charger does not have
output and battery voltage
is less than 10V/PC.
Contact your dealer.
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours

Chat with your FSP Clippers manual using AI

Get instant AI answers from your FSP Clippers manual

Ask anything about the FSP Clippers. Answers come from this manual, with the pages they are based on.

Clippers Maintenance Schedule

Remind me when maintenance is due
Every 2 months
Recharge battery during storage at 40 to 45 C

If storing the UPS in temperatures between 40C and 45C, recharge the battery every 2 months for 1-2 hours.

Show in the manual (page 31)
Every 3 months
Recharge battery during storage at -25 to 40 C

If storing the UPS in temperatures between -25C and 40C, recharge the battery every 3 months for 1-2 hours.

Show in the manual (page 31)

Free maintenance reminders

Timed to your purchase date. Always free, unsubscribe anytime.

By submitting you agree to the privacy policy. Unsubscribe with one click in any email.
M: qwen/qwen3.8-flash

Ask a Question

0/1000

Do you recommend Clippers?

Yes No

Frequently Asked Questions

A

The internal batteries typically last between 3 to 5 years depending on the operating ambient temperature. Higher temperatures can shorten battery life, so it is recommended to keep the unit in a cool environment.

Is this answer helpful?

A

Yes, but you must size the UPS appropriately. Laser printers have high power draws; ensure the UPS capacity exceeds the maximum power rating defined by the printer manufacturer to avoid overloading the system.

Is this answer helpful?

A

If a wiring fault is detected, the LCD will display a warning code and the alarm will sound. You should rotate the mains power socket by 180 degrees to correct line and neutral reversal issues.

Is this answer helpful?

A

No, the Emergency Power Off (EPO) function is disabled by default. To activate it, you must remove the metal plate connecting Pin 1 and Pin 2 on the EPO port and configure the logic via the LCD settings.

Is this answer helpful?

A

Yes, the unit supports remote monitoring via USB or RS-232 ports using included software. It also has an intelligent slot for optional SNMP or AS400 cards to enable web-based management.

Is this answer helpful?

A

You can set shorter backup time limits for the programmable outlets. This allows the UPS to shut down non-critical devices first, preserving battery power for mission-critical loads connected to general outlets.

Is this answer helpful?

M: QW-35-FL

Advantages and Disadvantages

Advantages

  • Delivers pure sine wave output ideal for sensitive electronics
  • Supports hot-swappable batteries for minimal downtime
  • Features comprehensive LCD monitoring and control interface
  • Offers flexible installation with tower and rack-mount options
  • Includes programmable outlets for smart load management
VS

Disadvantages

  • Requires specific compatible batteries for optimal performance
  • External battery packs add significant weight and size
  • Fan noise may be noticeable in quiet office environments
  • Initial setup requires reading safety warnings carefully
  • Limited to single-phase input power configurations
M: QW-35-FL

Product Specification

Type

Tower/Rackmount

Classification

VFI (On-Line)

Voltage

110-300V

Input

1x C14

Outputs

8x C13

Interfaces

USB, serial

Data Line Protection

N/A

Charging Time

3h (90%)

Features

LCD

Manufacturer Warranty

2 years

M: QW-35-FL

Product Description

FSP Clippers UPS: Reliable Power Protection for Your Critical Systems

Ensuring continuous power availability is essential for maintaining operational efficiency in both home and business environments. The FSP Clippers UPS series offers a robust solution designed to safeguard your sensitive electronics against power outages, surges, and fluctuations. With capacities ranging from 1KVA to 3KVA, these units provide the necessary backup time to allow for safe shutdowns or continued operation during unexpected grid failures.

These uninterruptible power supply systems feature advanced online double-conversion technology, delivering pure sine wave output that protects complex equipment like servers, medical devices, and networking gear. The user-friendly interface includes an intuitive LCD panel that displays real-time data on input voltage, battery status, load levels, and estimated runtime. Users can easily monitor system health and configure settings through the front panel buttons or via remote management software connected through USB, RS-232, or optional SNMP cards.

Installation is straightforward with options for both tower and rack-mount configurations. The design accommodates various regional plug types and supports external battery packs for extended autonomy. Safety is prioritized with built-in protections against overloads, short circuits, and overheating. The system also features programmable outlets that allow you to prioritize critical loads by automatically shutting down non-essential devices when battery power runs low. Regular maintenance is simplified with hot-swappable battery designs that minimize downtime during replacement procedures.

Whether you need to protect a single workstation or an entire server room, the FSP Clippers UPS delivers consistent performance with high efficiency modes that reduce energy consumption. Its compact form factor fits seamlessly into any environment while providing peace of mind knowing your data and hardware are secure.

Important Notes

  • Always ensure proper ventilation around the unit to prevent overheating.
  • Use only VDE-tested or CE-marked cables for all connections.
  • Replace batteries every 3 to 5 years depending on ambient temperature conditions.
M: QW-35-FL

© Copyright 2026 Manual.ly