Eaton 5PX 2200i RT2U G2 Manual

0.0 · 0 Ratings

PDF manual · 41 Pages

English

M: gpt-5.6-terra
page

/ 41

Loading...
c55f3aab479cdb11dbbdfab6f3bf51c54bce page 1e
614-40094-00
30
1.
2.
1.
2.
The number of Extended Battery Module is automatically detected, or can be set manually in number of EBM or in
Ah.
Deep discharge protection
This setting is recommended to avoid damaging the battery. Warranty is void if deep discharge protection is
disabled.
7.7 Retrieving the event log
To retrieve the event log through the display:
Press any button to activate the menu options, then select event log.
Scroll through the listed events.
7.8 Retrieving the fault log
To retrieve the fault log through the display:
Press any button to activate the menu options, then select fault log.
Scroll through the listed faults.
8 UPS maintenance
8.1 Equipment care
For the best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very
dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the equipment at an ambient temperature of 25 °C (77 °F).
The batteries are rated for a 3-5 year service life. The length of service life varies, depending on the frequency of usage
and ambient temperature (life divided by 2 each 10 °C above 25 °C).
If the UPS requires any type of transportation, verify that the UPS is turned off.
Batteries used beyond expected service life will often have severely reduced runtimes. Replace batteries at least every 4
years to keep units running at peak performance.
Batteries runtime will be reduced at low temperature (below 10 °C).
8.2 Storing the equipment
If you store the equipment for a long period, recharge the battery every 6 months by connecting the UPS toutility power.
The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommendsthat the batteries charge
for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has passed and the batteries were never
recharged, do not use them. Contact your servicerepresentative.

Chat with your Eaton 5PX 2200i RT2U G2 manual using AI

Get instant AI answers from your Eaton 5PX 2200i RT2U G2 manual

Ask anything about the Eaton 5PX 2200i RT2U G2. Answers come from this manual, with the pages they are based on.

5PX 2200i RT2U G2 Maintenance Schedule

Remind me when maintenance is due
Weekly
Perform automatic battery test

In constant charge mode, automatic battery tests are done every week by default. The UPS discharges batteries for 10 seconds under load to verify health.

Show in the manual (page 29)
Every 6 months
Recharge stored UPS batteries

If storing the equipment for a long period, recharge the battery every 6 months by connecting the UPS to utility power. Charge for 48 hours after storage.

Show in the manual (page 30)
Every 4 years
Replace internal batteries

Batteries are rated for a 3-5 year service life. Replace batteries at least every 4 years to keep units running at peak performance. A notification appears after 4 years.

Show in the manual (page 30)
Continuous
Keep area clean and dust free

For best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very dusty, clean the outside with a vacuum cleaner.

Show in the manual (page 30)

Free maintenance reminders

Timed to your purchase date. Always free, unsubscribe anytime.

By submitting you agree to the privacy policy. Unsubscribe with one click in any email.
M: qwen/qwen3.8-flash

Ask a Question

0/1000

Do you recommend 5PX 2200i RT2U G2?

Yes No

Frequently Asked Questions

A

The UPS is rated at 2200 VA and 2200 W. This unity power factor capacity makes it suitable for protecting demanding IT loads such as servers, switches, storage systems, and professional network equipment.

Is this answer helpful?

A

Yes. The RT2U design supports both standard 19-inch rack installation and vertical tower placement. Rack mounting hardware and tower supports are intended to support flexible deployment.

Is this answer helpful?

A

USB and RS232 communication ports are built in. LAN monitoring is available by installing a compatible optional network card, such as the Eaton Network-M2 Gigabit card, which supports HTTPS, SNMP, alerts, and environmental sensors.

Is this answer helpful?

A

Yes. The 5PX 2200i RT2U G2 supports compatible 72 V external battery modules. Up to four expansion battery modules can be connected to increase runtime for critical equipment.

Is this answer helpful?

A

It protects against outages, sags, surges, noise, and voltage variations. Automatic voltage regulation corrects certain input fluctuations without switching to battery power, while battery mode supplies power during a mains failure.

Is this answer helpful?

A

Yes. Programmable outlet groups allow selected loads to be managed independently. This can be used to shut down lower-priority equipment, schedule restarts, or preserve battery capacity for critical systems.

Is this answer helpful?

M: gpt-5.6-terra

Advantages and Disadvantages

Advantages

  • Provides 2200 W / 2200 VA capacity for servers, storage, and network equipment.
  • Rack or tower installation supports flexible deployment in IT rooms and cabinets.
  • USB, RS232, relay contacts, and optional LAN management enable broad monitoring options.
  • Programmable outlet groups can prioritize critical loads and conserve battery runtime.
  • Supports up to four compatible external battery modules for extended backup time.
VS

Disadvantages

  • The 2U model is relatively heavy at approximately 28.2 kg, requiring careful installation.
  • LAN connectivity requires an optional Network-M2 communication card.
  • Battery runtime depends heavily on connected load and installed external battery modules.
  • Internal batteries require planned replacement, typically after 3 to 5 years.
  • A 16 A input connection and suitable electrical infrastructure are required.
M: gpt-5.6-terra

Product Specification

Type

Tower/Rackmount

Classification

VI (Line-Interactive)

Apparent Power

2,200 VA

Real Power

2,200 W

Voltage

230 V

Input

1x C20

Outputs

8x C13, 2x C19

Interfaces

USB, serial, LAN

Data Line Protection

N/A

Runtime

10 min (50%)

Weight

62.17 lb

Dimensions (W x H x D)

17.24 x 3.37 x 23.74 in

Rack Units

2U

Special Features

LCD, HID support

Manufacturer Warranty

3 years (2 years battery)

M: gpt-5.6-terra

Product Description

Eaton 5PX 2200i RT2U Netpack G2 USB/serial/LAN Manual

The Eaton 5PX 2200i RT2U Netpack G2 is a high-capacity uninterruptible power supply designed to keep essential IT equipment operating through power disturbances. With a 2200 W / 2200 VA rating, this rack or tower UPS is suited to servers, storage devices, network hardware, and other business-critical systems that need dependable electrical protection.

Reliable Power Protection for Critical Loads

This model protects connected equipment from outages, voltage dips, surges, electrical noise, and overvoltage or undervoltage conditions. Its automatic voltage regulation helps maintain stable output during input fluctuations, reducing unnecessary battery use. During a utility failure, the UPS transfers to battery power to provide time for systems to continue operating or shut down safely.

The Eaton 5PX 2200i RT2U Netpack G2 USB/serial/LAN Manual keyword reflects the product's broad management capabilities. Standard USB and RS232 ports support local communication with connected systems, while network management can be added through a compatible Gigabit Network-M2 card. This option enables browser-based monitoring, HTTPS access, SNMP support, email alerts, and connection of environmental sensors.

Flexible Rack or Tower Deployment

The 2U chassis can be installed in a standard 19-inch rack or positioned vertically using tower supports. At 603 x 438 x 85.5 mm and approximately 28.2 kg, it is built for professional installations where space, stability, and service access matter. The unit includes IEC output connections, including a 16 A outlet for higher-demand equipment, plus programmable outlet groups for prioritizing loads.

Programmable segments allow administrators to restart devices in sequence, schedule shutdowns, or disconnect nonessential equipment during an extended outage. This can preserve battery runtime for core systems. For longer backup requirements, the UPS supports up to four compatible 72 V external battery modules.

Monitoring, Battery Care, and Service Options

A front LCD provides clear status details for load, battery capacity, runtime, events, alarms, and settings. Eaton's ABM battery management cycle is designed to optimize charging behavior and provide advance notice when battery replacement is approaching. Automatic and manual battery tests further help administrators monitor readiness.

Optional accessories broaden deployment possibilities. A HotSwap maintenance bypass can allow UPS service or replacement without interrupting connected loads, while FlexPDU units expand outlet distribution. Eaton Intelligent Power software can monitor power conditions and initiate controlled system shutdowns when battery capacity becomes low.

Note: Install the UPS indoors in a dry, ventilated location. Keep rear ventilation clearance, verify load requirements before connection, and use qualified personnel for battery service.

Note: Battery life is typically 3 to 5 years and is strongly affected by operating temperature. Keeping the environment near 25 C supports longer service life.

M: gpt-5.6-terra