WARNING, risk of DANGER! The operator must
refer to these instructions whenever this danger
symbol appears.
Equipment protected by double insulation.
Equipment suitable for live work.
Battery.
Earth.
The CE marking indicates conformity with
European directives, in particular LVD and EMC.
The rubbish bin with a line through it indicates that,
in the European Union, the product must undergo
selective disposal in compliance with Directive
WEEE 2012/19/EU. This equipment must not be
treated as household waste.

Measurement category IV corresponds to measurements
taken at the source of low-voltage installations.
Example: power feeders, counters and protection devices.
Measurement category III corresponds to measurements
on building installations.
Example: distribution panel, circuit-breakers, machines or

Measurement category II corresponds to measurements tak-
en on circuits directly connected to low-voltage installations.
Example: power supply to domestic electrical appliances
and portable tools.
Thank you for purchasing a C.A 742 voltage detector.
For best results from your instrument:
read these operating instructions carefully,
 the precautions for use.
ENGLISH

Chat with your Chauvin Arnoux CA 742 manual using AI

Get instant AI answers from your Chauvin Arnoux CA 742 manual

Ask anything about the Chauvin Arnoux CA 742. Answers come from this manual, with the pages they are based on.

Ask a Question

0/1000

Do you recommend CA 742?

Yes No

Frequently Asked Questions

A

The CA 742 indicates nominal voltage levels of 12, 24, 50, 127, 230, 400, and 690 V for AC or DC circuits. It also supports DC indication up to 750 V. It is intended for standardized voltage networks.

Is this answer helpful?

A

When voltage exceeds 50 V AC or 120 V DC, the red ELV indicator flashes and the tester emits audible beeps. The flashing rate increases as the detected voltage rises. Red bargraph indicators also accompany hazardous voltage ranges.

Is this answer helpful?

A

Yes. Connect the red probe to + and the black lead to COM, touch both probes together, and hold AUTO TEST. All indicators except ELV should illuminate and the audible signal should sound. Repeat the self-test after checks.

Is this answer helpful?

A

Yes. With no voltage detected, hold the continuity button while contacting the test points. A resistance below the continuity threshold causes sequential LED flashing and a continuous audible signal. The function is inhibited if voltage above 1 V is present.

Is this answer helpful?

A

No. The single-pole phase function can help locate a phase conductor on an earth-referenced system, but it is not an absence-of-voltage test. A non-flashing phase indicator does not prove that hazardous voltage is absent.

Is this answer helpful?

A

The CA 742 uses two 1.5 V AAA or LR3 alkaline batteries. Battery life is approximately 7,000 ten-second checks under specified conditions. If only alternating indicators light during self-test, replace the batteries.

Is this answer helpful?

M: gpt-5.6-terra

Advantages and Disadvantages

Advantages

  • IEC 61243-3 compliant two-pole voltage detector rated to 600 V CAT IV.
  • Detects nominal AC/DC voltage from 12 to 690 V, with DC indication up to 750 V.
  • Provides voltage absence checking, continuity indication, polarity indication, and phase identification.
  • IP65 protection, 2 m drop resistance, probe guards, and double insulation support field use.
  • AUTO TEST checks lead integrity, electronics, indicators, buzzer, and battery status before use.
VS

Disadvantages

  • It is a detector only; displayed indications must not be used as precision measurements.
  • Continuity testing is disabled when voltage greater than 1 V is present.
  • Phase detection does not prove that hazardous voltage is absent.
  • Live-circuit use is limited to a 30-second cycle followed by at least 240 seconds of rest.
  • Using the optional CA 751 adapter reduces the combined rating to CAT II 250 V.
M: gpt-5.6-terra

Product Specification

Measurement range

12-690 V

M: gpt-5.6-terra

Product Description

Chauvin Arnoux CA 742 Voltage Tester - Read, Download & Print Free

The Chauvin Arnoux CA 742 Voltage Tester is a compact two-pole safety tester made for qualified electrical professionals who need a clear, fast indication of voltage conditions. Designed for checking the absence of voltage before electrical work, it uses bright LED indicators and audible alerts to help users identify potentially hazardous circuits. Its automatic start-up supports efficient checks without a separate power switch.

Essential Voltage and Safety Functions

The CA 742 indicates nominal AC and DC voltage levels from 12 V to 690 V AC/DC, with DC detection available up to 750 V. A bargraph shows the detected range, while green and orange polarity lights identify DC polarity. For AC circuits, both polarity indicators illuminate. A red ELV warning indicator flashes and the unit beeps when hazardous voltage is detected above 50 V AC or 120 V DC.

The tester is rated to 600 V CAT IV and complies with IEC 61243-3 requirements for two-pole voltage detectors. This rating makes it suitable for demanding work around low-voltage installation sources, provided the stated operating limits and safety practices are followed. Double insulation, probe guards, IP65 ingress protection, and a 2 m drop rating add practical durability for indoor and outdoor electrical tasks.

More Than Voltage Indication

Alongside voltage detection, the CA 742 provides continuity and phase-identification functions. Hold the continuity button when no voltage is present to check a circuit: a low-resistance path triggers sequential flashing indicators and a continuous audible signal. The phase function uses a single probe to help locate phase conductors on grounded systems. However, phase indication must never replace an absence-of-voltage test.

A built-in self-test is an important safety feature. Before and after testing, users can touch the probes together and press AUTO TEST to verify the leads, electronics, indicators, buzzer, and battery condition. The tester is powered by two AAA or LR3 alkaline batteries, delivering approximately 7,000 ten-second checks under stated conditions.

Practical Design for Routine Checks

Measuring approximately 163 x 64 x 40 mm and weighing about 210 g, the CA 742 is easy to carry between jobs. It includes a red probe, black lead with probe, detachable strap, and rear storage for the probes. An optional CA 751 outlet adapter can support phase-to-neutral checks at sockets, although this combination is limited to CAT II 250 V.

Note: This is a voltage detector, not a precision measuring instrument. Perform the self-test, keep hands behind probe guards, inspect leads and insulation, and use only within the specified category and voltage limits.